ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 4/19/2013 BUILDING SURVEY DATE

Size: px
Start display at page:

Download "ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 4/19/2013 BUILDING SURVEY DATE"

Transcription

1 EAST PEABODY DRIVE CHAMPIAGN, ILLINOIS SYSTEM CONDITION INDEX.364 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 4,262,400 MUSEUM BUILDING GROSS SQUARE FEET 71,657 NUMBER OF BUILDING STORIES 2 BUILDING SURVEY DATE CCJM: Josh Polasky (M), Stanley Panek (E) ORIGINAL YEAR OF CONSTRUCTION /19/2013 B U I L D I N G D I S C I P L I N E R E P L A C E M E N T C O S T S U M M A R Y TRADE E X P E C T E D R E M A I N I N G S E R V I C E L I F E FAIR ($) GOOD ($) (5-10 YEARS) (10-20 YEARS) POOR ($) (1-5 YEARS) EXCELLENT ($) (20+ YEARS) TOTAL ($) $/GSF PERCENT OF BUILDING TOTAL (%) MECHANICAL 6, , ,800 1,319,600 1,674, PLUMBING 131, ,900 63, , FIRE PROTECTION 139, , ELECTRICAL 1,236, , ,500 1,471, COMMUNICATIONS 36, , , TOTAL % OF TOTAL 1,550, , ,000 1,451,100 4,262, NO CRITICAL ITEMS IDENTIFIED FOR THIS BUILDING NOTE: Cost Estimates are Construction Costs are in 2013 dollars to Replace in Kind unless otherwise noted PAGE 1

2 Text106 M E C H A N I C A L D I S C I P L I N E R E P L A C E M E N T C O S T S U M M A R Y CHILLED WATER SYSTEM PROCESS COOLING SYSTEM STEAM AND CONDENSTATE SYSTEM HEATING HOT WATER SYSTEM SUPPLY AIR SYSTEM HUMIDIFICATION SYSTEM TOILET EXHAUST SYSTEM KITCHEN EXHAUST SYSTEM HVAC CONTROLS SYSTEM SYSTEM/COMPONENT Chilled Water System Process cooling Steam and Condensate System Heating Hot Water System Air Handling System #1 Air Handling System #2 Humidification Toilet exhaust Kitchen Exhaust System HVAC controls MECHANICAL TOTAL % OF TOTAL POOR (1-5 YEARS) E X P E C T E D R E M A I N I N G S E R V I C E L I F E FAIR GOOD (5-10 YEARS) (10-20 YEARS) EXCELLENT (20+ YEARS) TOTAL 121, ,800 21,600 21,600 70,300 70, , , , , , ,800 50,800 50,800 6,200 6,200 21,400 21, , ,400 6, , ,800 1,319,600 1,674, PAGE 2

3 Text6 C H I L L E D W A T E R S Y S T E M A S S E S S M E N T D A T A Item ID Description Building was connected to campus chilled water loop in Existing chillers and cooling tower was removed Overall Condition Excellent Date Installed Remaining Useful Life 40 Years Nominal Useful Life: 30 Years Replacement Cost $121, PAGE 3

4 Text6 P R O C E S S C O O L I N G A S S E S S M E N T D A T A Item ID Description Condensing unit serving data room Overall Condition Good Date Installed 1/1/2000 Remaining Useful Life 10 Years Nominal Useful Life: 30 Years Manufacturer Liebert Size/Capacity 3 ton Voltage 208 V Replacement Cost $21,600 Text6 P R O C E S S C O O L I N G S U R V E Y P H O T O G R A P H S Condensing unit PAGE 4

5 Text6 S T E A M A N D C O N D E N S A T E S Y S T E M A S S E S S M E N T D A T A Item ID Description Campus steam has been utilized for building heat. Two steam/hot water heat exchangers are utilized. Two condensate pumps return condensate to campus loop. Overall Condition Excellent Date Installed 1/1/2012 Remaining Useful Life 25 Years Nominal Useful Life: 30 Years Equipment Tag HX-1,2 Manufacturer Bell & Gossett Size/Capacity 632,1312 LBS/HR Voltage 480 V Replacement Cost $70, PAGE 5

6 Text6 S T E A M A N D C O N D E N S A T E S Y S T E M S U R V E Y P H O T O G R A P H S Condensate Pump CP-1 Condensate pump CP-2 Heat exchanger-1988 Heat Exchanger PAGE 6

7 Text6 H E A T I N G H O T W A T E R S Y S T E M A S S E S S M E N T D A T A Item ID Description Heating hot water pumps. #2 and #4 is stand-by. Overall Condition Excellent Date Installed 1/1/2012 Remaining Useful Life 25 Years Nominal Useful Life: 30 Years Equipment Tag HWP-1,2,3,4 Manufacturer B&G Model Number 80 SC Size/Capacity 65,65,150,150 GPM HP/kW 5, 5, 7.5, 7.5 Voltage 208 V Replacement Cost $520, PAGE 7

8 Text6 H E A T I N G H O T W A T E R S Y S T E M S U R V E Y P H O T O G R A P H S Pump motor nameplate Hot water Pumps Steam to Hot Water heat Exchanger Hot water heater in Mech Room PAGE 8

9 Text6 A I R H A N D L I N G S Y S T E M # 1 A S S E S S M E N T D A T A Description Overall Condition Date Installed 1/1/2012 Equipment Tag Item ID Manufacturer Six new and one original unit LS-7 serve original museum space and 1968 addition. All units have cooling coils. DOAS-1 and 2 have hot water heating coils and heat recovery wheel. Excellent Remaining Useful Life 25 Years Nominal Useful Life: 30 Years Size/Capacity ASU-1,2, GS-5,6, ASU-1,2, DOAS-1,2, LS-7 AIR Flow Equipment/Buffalo HP/kW 25,15,25,10,15,15,3 Voltage Replacement Cost $585,900 16,800 CFM, 7,500 CFM, 16,000CFM, 6,000CFM,15,000CFM, 6,200CFM,6,800 CFM 208 V PAGE 9

10 Text6 A I R H A N D L I N G S Y S T E M # 1 S U R V E Y P H O T O G R A P H S Air handling unit DOAS-1 Air handling unit ASU-1 Nameplate at ASU-1 Nameplate at DOAS PAGE 10

11 Text6 A I R H A N D L I N G S Y S T E M # 2 A S S E S S M E N T D A T A Item ID Description Unit AHU-1 serves 1987 addition. Unit supplies air to 10 fan powered boxes. Overall Condition Fair Date Installed 1/1/1987 Remaining Useful Life Years Nominal Useful Life: 30 Years Equipment Tag AHU-1 Manufacturer BOHN Size/Capacity 16,900 HP/kW 20 Voltage 480 V Recommendation Replacement with constant air system and dedicated humidification unit. Replacement Cost $143,800 Critical Issues Control of humidity due to building envelope, windows type and HVAC distribution system PAGE 11

12 Text6 A I R H A N D L I N G S Y S T E M # 2 S U R V E Y P H O T O G R A P H S Fan Power box for Room #6 Air handling unit-ahu-1 Fan powered boxes PAGE 12

13 Text6 H U M I D I F I C A T I O N A S S E S S M E N T D A T A Item ID Description Steam humidifiers serving units original building and 1968 addition. Overall Condition Good Date Installed 1/1/2012 Remaining Useful Life 19 Years Nominal Useful Life: 20 Years Manufacturer Dristeem Recommendation Provide new humidification unit for AHU-1 Replacement Cost $50,800 Critical Issues AHU-1 utilizes campus steam foe humidification. Text6 H U M I D I F I C A T I O N S U R V E Y P H O T O G R A P H S Humidifier nameplate Water treatment for humidification Humidifier PAGE 13

14 Text6 T O I L E T E X H A U S T A S S E S S M E N T D A T A Item ID Description Toilet exhaust fan serving basement washrooms Overall Condition Poor Date Installed 1/1/1961 Remaining Useful Life Exceeded Nominal Useful Life: 30 Years Replacement Cost $6, PAGE 14

15 Text6 K I T C H E N E X H A U S T S Y S T E M A S S E S S M E N T D A T A Item ID Description Exhaust fan serving Café area Overall Condition Excellent Date Installed 1/1/2012 Remaining Useful Life 25 Years Nominal Useful Life: 30 Years Equipment Tag EF-1 Size/Capacity 4500 CFM HP/kW.75 Voltage 208 V Recommendation Improve air separation or relocate café. Replacement Cost $21,400 Critical Issues Café exhaust and supply air interfere with museum humidification control PAGE 15

16 Text6 K I T C H E N E X H A U S T S Y S T E M S U R V E Y P H O T O G R A P H S Café exhaust PAGE 16

17 Text6 H V A C C O N T R O L S A S S E S S M E N T D A T A Description New digital control and BAS were installed for air handling units installed in Pneumatic controls serve existing unit AHU-1 (1987 addition). During Spring 2013 work was in progress to add digital controls to existing pneumatic control serving AHU-1 and fan power boxes. Overall Condition Date Installed 1/1/2012 Manufacturer Recommendation Item ID Critical Issues Good Remaining Useful Life 15 Years Nominal Useful Life: 18 Years Siemens Replacement Cost $132,400 Separate Cafe HVAC system from museum system or relocate Café to other space. Control of humidity in all exhibit spaces. Problem with Pavilion space due to building envelope, window types and 1987 air distribution utilizing fan powered VAV boxes. Text6 H V A C C O N T R O L S S U R V E Y P H O T O G R A P H S Controls at air handling unit. Installation of new controls in Mech room #01 Controls in head house PAGE 17

18 Text106 P L U M B I N G D I S C I P L I N E R E P L A C E M E N T C O S T S U M M A R Y DOMESTIC COLD WATER SYSTEM HEATER PLUMBING FIXTURES SYSTEM SANITARY WASTE AND VENT SYSTEM SUB-SOIL DRAINAGE SYSTEM SYSTEM/COMPONENT Domestic Cold Water System Hot Water Heater Plumbing Fixtures Sanitary Waste and Vent Sub Soil Drainage and Storm System PLUMBING TOTAL % OF TOTAL POOR (1-5 YEARS) E X P E C T E D R E M A I N I N G S E R V I C E L I F E FAIR GOOD (5-10 YEARS) (10-20 YEARS) EXCELLENT (20+ YEARS) TOTAL 114, ,900 16,400 16,400 63,000 63, , , , , , ,900 63, , PAGE 18

19 Text6 D O M E S T I C C O L D W A T E R S Y S T E M A S S E S S M E N T D A T A Item ID Description Domestic cold water service is located in mechanical room #50 and shared with Art and Design Building. Overall Condition Poor Date Installed 1/1/1961 Remaining Useful Life Exceeded Nominal Useful Life: 50 Years Recommendation Replace with new piping Replacement Cost $114, PAGE 19

20 Text6 H O T W A T E R H E A T E R A S S E S S M E N T D A T A Item ID Description Domestic hot water tank is located in mechanical room# 50 and shared with Art and Design Building Overall Condition Poor Date Installed 1/1/1961 Remaining Useful Life Exceeded Nominal Useful Life: 25 Years Recommendation Replace with new hot water system. Replacement Cost $16, PAGE 20

21 Text6 P L U M B I N G F I X T U R E S A S S E S S M E N T D A T A Item ID Description Plumbing fixtures-(2) urinals, (7)water closets, (7)lavatories,(1) mop basin and Café kitchen sink Overall Condition Good Date Installed 1/1/1987 Remaining Useful Life 20 Years Nominal Useful Life: 50 Years Replacement Cost $63,000 Text6 P L U M B I N G F I X T U R E S S U R V E Y P H O T O G R A P H S Mop basin Urinals Toilet room PAGE 21

22 Text6 S A N I T A R Y W A S T E A N D V E N T A S S E S S M E N T D A T A Item ID Overall Condition Fair Date Installed 1960,1987 Remaining Useful Life 10 Years Nominal Useful Life: 50 Years Replacement Cost $170,000 Text6 S A N I T A R Y W A S T E A N D V E N T S U R V E Y P H O T O G R A P H S Sewage ejector #1 Sewage ejector # PAGE 22

23 Text6 S U B S O I L D R A I N A G E A N D S T O R M S Y S T E M A S S E S S M E N T D A T A Item ID Overall Condition Fair Date Installed 1960,1987 Remaining Useful Life 10 Years Nominal Useful Life: 50 Years Replacement Cost $232,900 Critical Issues Seepage in Basement Rm#71.Removal of pit collecting water at east side of the building. Text6 S U B S O I L D R A I N A G E A N D S T O R M S Y S T E M S U R V E Y P H O T O G R A P H S Sump pump Pit collecting water east side PAGE 23

24 Text106 F I R E P R O T E C T I O N D I S C I P L I N E R E P L A C E M E N T C O S T S U M M A R Y FIRE ALARM SYSTEM SYSTEM/COMPONENT Fire Alarm System FIRE PROTECTION TOTAL % OF TOTAL POOR (1-5 YEARS) E X P E C T E D R E M A I N I N G S E R V I C E L I F E FAIR GOOD (5-10 YEARS) (10-20 YEARS) EXCELLENT (20+ YEARS) TOTAL 139, , , , PAGE 24

25 Text6 F I R E A L A R M S Y S T E M A S S E S S M E N T D A T A Item ID Description Fire alarm system includes pull stations, horns, strobes and smoke detectors. Overall Condition Poor Date Installed 1/1/1986 Remaining Useful Life Exceeded Nominal Useful Life: 20 Years Equipment Tag - Manufacturer Cerberus/Pyrotronics Model Number MXL Serial Number - Size/Capacity - HP/kW - Voltage - Material - Recommendation Upgrade to new campus standard system Replacement Cost $139,900 Critical Issues Maintenance of smoke detectors PAGE 25

26 Text6 F I R E A L A R M S Y S T E M S U R V E Y P H O T O G R A P H S Fire alarm devices Fire Alarm panel Fire alarm signal box Smoke detector PAGE 26

27 Text106 E L E C T R I C A L D I S C I P L I N E R E P L A C E M E N T C O S T S U M M A R Y SUBSTATION LOW VOLTAGE SYSTEM EMERGENCY POWER SYSTEM INTERIOR LIGHTING EMERGENCY LIGHTING SYSTEM EXIT LIGHTING SYSTEM LIGHTING CONTROL SYSTEM EXTERIOR LIGHTING SYSTEM SYSTEM/COMPONENT Substation #1 Substation #2 Low Voltage Distribution Emergency Power System Interior Lighting Emergency Lighting System Exit Lighting System Lighting Control System Exterior Lighting ELECTRICAL TOTAL % OF TOTAL POOR (1-5 YEARS) E X P E C T E D R E M A I N I N G S E R V I C E L I F E FAIR GOOD (5-10 YEARS) (10-20 YEARS) EXCELLENT (20+ YEARS) TOTAL 131, , , , , ,600 33,600 33, , ,100 22,500 22,500 18,100 18, , ,800 27,600 27,600 1,236, , ,500 1,471, PAGE 27

28 Text6 S U B S T A T I O N # 1 A S S E S S M E N T D A T A Item ID Description Substation with 5KV fused load break switch, 500 KVA transformer and 800 A main switch,(6) fuse/switches for low voltage distribution. Service for 1986 Addition. Overall Condition Excellent Date Installed 1/1/2001 Remaining Useful Life 30 Years Nominal Useful Life: 40 Years Equipment Tag - Manufacturer Square D Model Number - Serial Number B Size/Capacity 800 A HP/kW - Voltage 4160/277/480 V Material Copper bus Recommendation - Replacement Cost $131, PAGE 28

29 Text6 S U B S T A T I O N # 1 S U R V E Y P H O T O G R A P H S Transformer nameplate Substation #1 and #2 Substation nameplate Primary section PAGE 29

30 Text6 S U B S T A T I O N # 2 A S S E S S M E N T D A T A Item ID Description Substation with 100A primary switch, 225KVA transformer and 800A main breaker. Service original section of Museum Overall Condition Poor Date Installed 1/1/1968 Remaining Useful Life Exceeded Nominal Useful Life: 40 Years Equipment Tag - Manufacturer Sorgel Model Number - Size/Capacity 800 A HP/kW - Voltage 12470/120/208 V Material Copper bus Recommendation Krannert Museum and Art And Design Building power distribution is intermixed. Replacement of original equipment is recommended. Replacement Cost $144,200 Comments Substation #2 is located in Art And Design Building RM # PAGE 30

31 Text6 S U B S T A T I O N # 2 S U R V E Y P H O T O G R A P H S Substation #2 Substation tag PAGE 31

32 Text6 L O W V O L T A G E D I S T R I B U T I O N A S S E S S M E N T D A T A Description 120/208 V Substation #2 provides power to panelboards and motor control center located within original section of the building. 277/480 V Substation #1 provides power to panelboards and equipment locate at 1986 addition. Two distribution panelboards were added in 2012 to serve new HVAC equipment. Overall Condition Date Installed 1961,1986 and 2012 Equipment Tag - Manufacturer Model Number - HP/kW - Material - Recommendation Item ID Poor Remaining Useful Life Exceeded includes original equipment Nominal Useful Life: 40 Years Serial Number - Size/Capacity - Voltage Square D Replacement Cost $545, /208V and 277/480 V Krannert Museum and Art And Design Building power is intermix. Replacement of original equipment from 1961 is recommended PAGE 32

33 Text6 L O W V O L T A G E D I S T R I B U T I O N S U R V E Y P H O T O G R A P H S Typical panelboard Distribution Panelboard DP-1,2(1986) Motor control center Distribution Panelboard PAGE 33

34 Text6 E M E R G E N C Y P O W E R S Y S T E M A S S E S S M E N T D A T A Description Overall Condition Date Installed 1/1/1986 Equipment Tag - Manufacturer Model Number HP/kW - Material - Recommendation Item ID Comments Emergency distribution system in 1986 expansion includes emergency panelboard EM-1 and two sets of battery systems. Each set include control /relay panel with inverter and the battery bank. Portion of the building constructed in 1961 receives emergency service from Art And Design building. Poor Remaining Useful Life Exceeded Nominal Useful Life: 25 Years Serial Number - Size/Capacity Voltage Replacement Cost $33,600 Manville Products Corporation 6 KVA 120 V Installation of emergency generator. Subject to battery replacement PAGE 34

35 Text6 E M E R G E N C Y P O W E R S Y S T E M S U R V E Y P H O T O G R A P H S Emergency battery system A and B Emergency battery System Emergency battery Emergency Panelboard EM PAGE 35

36 Text6 I N T E R I O R L I G H T I N G A S S E S S M E N T D A T A Description Overall Condition Interior lighting includes track lighting, down lights, wall washing lighting, art display lighting and general lighting. Majority of fixtures have incandescent lamps. Auditorium lighting was installed in Date Installed 1961, 1986 and 2000 Equipment Tag - Manufacturer - Model Number - HP/kW - Material - Recommendation Item ID Poor Remaining Useful Life Exceeded except Auditorium and localized display lights Nominal Useful Life: 25 Years Serial Number - Size/Capacity - Voltage 120 V Replacement Cost $445,100 Conduct study with lighting consultant related to updates and replacement of lighting system PAGE 36

37 Text6 I N T E R I O R L I G H T I N G S U R V E Y P H O T O G R A P H S Typical display lighting Art gallery lighting Art storage lighting Auditorium lighting PAGE 37

38 Text6 E M E R G E N C Y L I G H T I N G S Y S T E M A S S E S S M E N T D A T A Description Overall Condition Item ID Date Installed 1/1/1986 Equipment Tag - Manufacturer - Model Number - Serial Number - Size/Capacity - HP/kW - Material - Recommendation - Emergency circuits originated from emergency panelboards provide power to selected light fixtures located in stairways, corridors and auditorium. Battery banks power will provide service to emergency panelboards during loss of utility service. Auditorium is equipped with an additional light fixture units with self contained battery back- up. Poor Remaining Useful Life Exceeded Nominal Useful Life: 25 Years Voltage 120 V Replacement Cost $22, PAGE 38

39 Text6 E M E R G E N C Y L I G H T I N G S Y S T E M S U R V E Y P H O T O G R A P H S Dual heads battery in lighting in auditorium Gallery lighting-emergency fixtures located every 30 feet PAGE 39

40 Text6 E X I T L I G H T I N G S Y S T E M A S S E S S M E N T D A T A Item ID Description Edge glow (or box style) exit sign with two fluorescent lamps. Overall Condition Poor Date Installed 1961 and 1986 Remaining Useful Life Exceeded Nominal Useful Life: 25 Years Equipment Tag - Manufacturer Alco Serial Number - Size/Capacity - HP/kW - Voltage 120 V Material - Recommendation Replace with LED type battery back up signs Replacement Cost $18, PAGE 40

41 Text6 E X I T L I G H T I N G S Y S T E M S U R V E Y P H O T O G R A P H S Green color exit signat main entry Box type exit sign Edge glow type exit sign PAGE 41

42 Text6 L I G H T I N G C O N T R O L S Y S T E M A S S E S S M E N T D A T A Item ID Description Auditorium is equipped with dimming system manufactured by Lutron. Selected gallery lights have local wall mounted dimmers. Overall Condition Good Date Installed 1/1/2000 Remaining Useful Life 5 Years Nominal Useful Life: 20 Years Equipment Tag - Manufacturer Lutron Model Number - Serial Number - Size/Capacity - HP/kW - Voltage - Material - Recommendation - Replacement Cost $103, PAGE 42

43 Text6 L I G H T I N G C O N T R O L S Y S T E M S U R V E Y P H O T O G R A P H S Auditorium dimming Wall mounted dimmers PAGE 43

44 Text6 E X T E R I O R L I G H T I N G A S S E S S M E N T D A T A Item ID Description Exterior illumination is provided by typical campus pole mounted fixtures and recessed fixtures installed at each entry Overall Condition Poor Date Installed 1/1/1986 Remaining Useful Life Exceeded Nominal Useful Life: 25 Years Equipment Tag - Manufacturer - Model Number - Serial Number - Size/Capacity - HP/kW - Voltage 120 V Material - Recommendation Installation of additional lighting Replacement Cost $27, PAGE 44

45 Text6 E X T E R I O R L I G H T I N G S U R V E Y P H O T O G R A P H S Back entry fixtures Canopy light over main entry Wall washing fixture behind decorative grillage Front of the building PAGE 45

46 Text106 C O M M U N I C A T I O N S D I S C I P L I N E R E P L A C E M E N T C O S T S U M M A R Y DATA SYSTEM SECURITY ACCESS CONTROL SYSTEM CCTV SYSTEM SYSTEM/COMPONENT Communication Infrastructure System Access Control System Intrusion Detection System CCTV System COMMUNICATIONS TOTAL % OF TOTAL POOR (1-5 YEARS) E X P E C T E D R E M A I N I N G S E R V I C E L I F E FAIR GOOD (5-10 YEARS) (10-20 YEARS) EXCELLENT (20+ YEARS) TOTAL 260, ,600 24,200 24,200 36,600 36,600 57,700 57,700 36, , , PAGE 46

47 Text6 C O M M U N I C A T I O N I N F R A S T R U C T U R E S Y S T E M A S S E S S M E N T D A T A Item ID Description The building is fed with 12 strands of single mode fiber and 300 copper pairs with each pair grounded and individually protected by a fuse/surge arrestor. Fiber and copper originate from Node #2. The building IDF is located in room 45 on the basement level of Building 219. Fiber distributes radially from the building IDF to hub rooms (telecommunication rooms) to within 100 meters of end-use equipment and lands at rack mounted fiber switches within the hub room. Overall Condition There are two hub rooms located within the building Hub A is located in room 10 (one rack and punch down blocks) and Hub B is located in room 64A (two racks). Hub rooms are organized to feed multiple floors. Typically, each hub room is equipped with free standing racks, wire management, and overhead basket tray. Each hub has a technology ground bar tied into the building grounding system. Hub B has a dedicated electrical panel. Hub A and B are monitored by a smoke detector. Hub B has a dedicated Liebert split unit with a remote condensing unit. Outlet standards typically have 1"C stubbed to cable management. Standard outlet consists of two network cables and two data jacks. Station cable consists of Cat 6e (Mohawk Advancenet). The building is typically equipped with WIFI throughout (coverage not noted). Good Date Installed UIUC network upgrade complete (date range 2006 to 2012) Remaining Useful Life 20 Years Nominal Useful Life: 20 Years Replacement Cost $260, PAGE 47

48 Text6 C O M M U N I C A T I O N I N F R A S T R U C T U R E S Y S T E M S U R V E Y P H O T O G R A P H S Building 220 IDF Fiber Building 220 Hub A Building 220 Hub B Building 220 IDF Copper PAGE 48

49 Text6 A C C E S S C O N T R O L S Y S T E M A S S E S S M E N T D A T A Item ID Description Card access system to restrict entrance to the building and individual rooms. Monitoring equipment is located in Security office -Room 174 Overall Condition Good Date Installed 1/1/2010 Remaining Useful Life 17 Years Nominal Useful Life: 20 Years Equipment Tag - Manufacturer - Model Number - Serial Number - Size/Capacity - HP/kW - Voltage - Material - Recommendation - Replacement Cost $24,200 Comments Security office personnel requested installation of an additional outlets and power for equipment PAGE 49

50 Text6 A C C E S S C O N T R O L S Y S T E M S U R V E Y P H O T O G R A P H S Card reader at exterior door TV monitor in security office Interior card reader PAGE 50

51 Text6 I N T R U S I O N D E T E C T I O N S Y S T E M A S S E S S M E N T D A T A Item ID Description Motion detection system to notify /alarm unauthorized access to the building or selected area. Monitoring equipment is located in Security office -Room 174 Overall Condition Poor Date Installed 1/1/2000 Remaining Useful Life 5 Years Nominal Useful Life: 20 Years Equipment Tag - Manufacturer - Model Number - Serial Number - Size/Capacity - HP/kW - Voltage - Material - Recommendation Connection to campus security office Replacement Cost $36,600 Comments Security office personnel requested installation of an additional outlets and power for equipment PAGE 51

52 Text6 I N T R U S I O N D E T E C T I O N S Y S T E M S U R V E Y P H O T O G R A P H S Motion detector in gallery TV monitor in security office Motion detector in open area PAGE 52

53 Text6 C C T V S Y S T E M A S S E S S M E N T D A T A Item ID Description CCTV for monitoring gallery area. Monitoring equipment is located in Security office -Room 174 Overall Condition Good Date Installed 1/1/2010 Remaining Useful Life 17 Years Nominal Useful Life: 20 Years Equipment Tag - Manufacturer - Model Number - Serial Number - Size/Capacity - HP/kW - Voltage - Material - Recommendation - Replacement Cost $57, PAGE 53

54 Text6 C C T V S Y S T E M S U R V E Y P H O T O G R A P H S TV monitor in security office TY camera PAGE 54

55 Text6 L E G A C Y A S S E T D E S C R I P T I O N : K R A N N E R T A R T M U S E U M The Krannert Art Museum contains two floors and a basement. The building consists of mechanical and electrical rooms, building service storage, lounges, administrative offices, conference rooms, a classroom, a study room, and exhibition areas. The Life Safety Code classifies the building as Mixed Occupancy (part Assembly, part Business). The assembly occupancy is located in the first floor (Room 150, 101, 108, 109, 114, 162, 164A, 166, and 170) and the basement floor (Room 002, 006, 007, 011, 060, 062, 066, 068). The Krannert Art Museum has a manual and automatic fire alarm system. Manual pull stations are located at all exits in floors two through basement. Automatic fire detection is located in the second floor (Stair 4, 5, Room 203, 202, and 201), the first floor (the entire floor), and the lower floor (the entire floor). The occupant notification is by audible/visual and visual devices. The audible/visual devices are located in the second floor (near Stair 4 and 5); the first floor (Room 108 and 113); and the lower floor (Room 013, 011, 002, 070, 052). The visual devices are located in the lower floor (Room 062 and 001). The fire alarm control panel for the building, located on the first floor Stair 2, is Cerebus Pyrotronics model XL3. The Krannert Art Museum has battery-operated emergency lights located in the basement floor (Room 062). 12 batteries located in Room 014 supply emergency power to the building. The Krannert Art Museum is essentially a non-sprinklered building with less than 6 sprinklers located in the lower floor (Room 074 and 069). There exists a Class II standpipe system located only within the basement mechanical room 050. There exists no fire department connection into the building. OCCUPANT LOAD/EXITING Second Floor: 55 occupants; two exits required (2 exits provided); the exit width including stairs/doors provides capacity for 312 occupants. Door and stair widths are sufficient for occupants served. First Floor (LED): 1575 occupants; 4 exits required (8 exits provided); 315" exit door width required (413" provided); door and corridor widths are sufficient for occupants served. Basement Floor: 914 occupants; three exits required (5 exits provided); the exit width including stairs/doors provides capacity for 898 occupants. Door and stair widths are sufficient for occupants served PAGE 55

56 K R A N N E R T A R T M U S E U M L E G A C Y A S S E S S M E N T S U M M A R Y Item ID REQUIREMENT NUMBER INSPECTION DATE IDENTIFIED ISSUE LEGACY VALUE PERCENT COMPLETE GENERAL LEGACY ITEMS ITEMS REQ /1/2006 Flooring: Replace VAT - Floor Basement 42, ,000 42, REQ /1/2006 Asbestos Abatement: Noted Hazard In Building 18, ,500 18, REQ /1/2006 Exterior Wall: Caulk. 67, ,100 67, REQ /1/2006 Windows: Recondition 9, ,900 9, REQ /1/2006 Structure: Investigate 2, ,400 2, REQ /1/2006 Exterior Walls: Repair Cracks 39, ,100 39, REQ /1/2006 Flooring: Repair Concrete 7, ,100 7, REQ /1/2006 Roof: Replace Built-Up With EPDM 222, , , REQ /1/2002 Efflorescence: Water Damage 3, ,600 3, REQ /1/2006 Fire Barrier: Unprotected Penetrations 4, ,400 4, REQ /17/2005 Means of Egress: Discharge from Exits 39, ,700 39, REQ /17/2005 Means of Egress: Interruption of Exit Stair 16, ,400 16, REQ /17/2005 Means of Egress: Capacity 27, ,700 27, REQ /17/2005 Means of Egress: Stair Enclosure 15, ,400 15,400 POOR FAIR CODE TOTAL GENERAL LEGACY ITEMS TOTALS 515, ,600 60, ,200 MEP LEGACY ITEMS ITEMS REQ REQ /17/2005 Underground Structure: No A/S 345, , ,600 6/17/2005 Vertical Openings: Atrium 271, , ,400 Poor = VFA Priorities 1,2, and 3; Fair VFA Priority 4; and Code VFA Priority 5 MEP LEGACY ITEMS TOTALS 617, , ,000 TOTALS 1,132, ,071,700 60,600 1,132,200 % OF LEGACY VALUE PAGE 56

57 Text6 L E G A C Y A S S E S S M E N T D A T A : R E Q Date Inspected 12/1/2006 Description Requirement Category Requirement Name Condition During our investigation we encountered a number of areas throughout the building that may contain asbestos floor tile or linoleum. The flooring in many areas has exceeded its expected useful life and should be replaced. This flooring should be removed and replaced with UIUC approved floor covering (VCT). Asbestos Flooring: Replace VAT - Floor Basement (Legacy) Critical Percent Complete 0.0 Recommendation Replace flooring as indicated. Approximately $2 / square foot as provided by Operations and Maintenance Estimated Cost 42, Estimated Remaining Cost: 42, Text6 L E G A C Y A S S E S S M E N T D A T A : R E Q Date Inspected 12/1/2006 Description Requirement Category Requirement Name Condition This building exhibits friable asbestos. The hazards asbestos as noted does not comply with EPA relations, section of 40 CFR 763 "Friable Asbestos- Containing Materials in Schools " Identification and Notification as set forth in the AHERA Regulations. See correction for more information. Asbestos Asbestos Abatement: Noted Hazard In Building (Legacy) Critical Percent Complete 0.0 Recommendation Remove all friable asbestos Lower lover mechanical room - Rm Approximate costs have been determined by the square footage. This pricing is for budgetary purposes only and not intended for contract review. Estimated Cost 18, Estimated Remaining Cost: 18, PAGE 57

58 Text6 L E G A C Y A S S E S S M E N T D A T A : R E Q Date Inspected 12/1/2006 Description Requirement Category Requirement Name Condition All exterior caulk has started to crack and separate. The old caulk should be removed and new installed. Integrity Exterior Wall: Caulk. (Legacy) Poor Percent Complete 0.0 Recommendation Provide new caulking as specified. Specifically caulking at dark marble belt, vertical caulking east side of entrance by metal lattace, around metal siding at all windows and where metal joins masonry. Estimated Cost 67, Estimated Remaining Cost: 67, Action Date 12/1/2009 Text6 L E G A C Y A S S E S S M E N T D A T A : R E Q Date Inspected 12/1/2006 Description Requirement Category Requirement Name Condition The windows on the north side of the Kinkead section are non-operable metal framed with insulating glass. These units are in poor to fair condition due to age, deteriorated sealant and glazing compound, some water infiltration. Many of the windows leak air and water. The building is considered architecturally significant and replacement of the windows is not a viable option. Therefore the windows should be scraped, reglazed as necessary and repainted. Integrity Windows: Recondition (Legacy) Poor Percent Complete 0.0 Recommendation Recondition existing windows frames and glazing. Allowance for damaged trim and sashes. Estimated Cost 9, Estimated Remaining Cost: 9, Action Date 12/1/ PAGE 58

59 Text6 L E G A C Y A S S E S S M E N T D A T A : R E Q Date Inspected 12/1/2006 Description Requirement Category Requirement Name Condition Some structural problems exist in this building. Floors are not level and show signs of settlement throughout the building. The second floor walls are exhibiting cracks that appear to be structural in nature. Integrity Structure: Investigate (Legacy) Poor Percent Complete 0.0 Recommendation Costs for structural evaluation. Estimated Cost 2, Estimated Remaining Cost: 2, Action Date 12/1/2007 Text6 L E G A C Y A S S E S S M E N T D A T A : R E Q Date Inspected 12/1/2006 Description Requirement Category Requirement Name Condition There are cracks in the exterior marble columns that do not appear to be structural. Integrity Exterior Walls: Repair Cracks (Legacy) Poor Percent Complete 0.0 Recommendation The cracks need to be cleaned of loose material and patched and sealed with an epoxy to prevent further deterioration. Estimated Cost 39, Estimated Remaining Cost: 39, Action Date 12/1/ PAGE 59

60 Text6 L E G A C Y A S S E S S M E N T D A T A : R E Q Date Inspected 12/1/2006 Description Requirement Category Requirement Name Condition The concrete floors in the basement shop areas have numerous cracks. Integrity Flooring: Repair Concrete (Legacy) Poor Percent Complete 0.0 Recommendation Repair concrete floors and refinish as required. Estimated Cost 7, Estimated Remaining Cost: 7, Action Date 12/1/2011 Text6 L E G A C Y A S S E S S M E N T D A T A : R E Q Date Inspected 12/1/2006 Description Requirement Category Requirement Name Condition The existing built-up roofing exhibits signs of membrane slippage, blisters, and/or flashing failures. Entire roof system will require replacement. Integrity Roof: Replace Built-Up With EPDM (Legacy) Poor Percent Complete 0.0 Recommendation Replace existing built-up roof on Sections A - C. Although assessment criteria calls for replacemnt in kind there are other dorm buildings with newer roofs that are EPDM. In addition, site staff indicated the built up roof over the Peabody building is to be replaced with an EPDM roofing system. There are therefore, clear indications the university intends to replace built-up roofs with EPDM roofing systems. Sections D and E currently have EPDM loose/ballasted roofing, however the staff reports that the insulation is wet. Recommend further investigation as to the condition of sections D & E. Estimated Cost 222, Estimated Remaining Cost: 222, Action Date 12/1/ PAGE 60

61 Text6 L E G A C Y A S S E S S M E N T D A T A : R E Q Date Inspected 12/1/2002 Description Requirement Category Requirement Name Condition Staff reported that the walls in the basement storage area are experiencing some efflorescence or water damage and should be repaired. The damage could be due to concealed deficiency conditions of either the roof or wall leak. See correction for locations. Integrity Efflorescence: Water Damage (Legacy) Poor Percent Complete 0.0 Recommendation Subsequent to, or in conjunction with, repair of source of damage, patch and seal the walls in basement mechanical rooms. The walls may need to be coated with an epoxy product to seal out the water. Estimated Cost 3, Estimated Remaining Cost: 3, Action Date 12/1/2005 Text6 L E G A C Y A S S E S S M E N T D A T A : R E Q Date Inspected 12/1/2006 Description Requirement Category Requirement Name Condition There exists ductwork, conduit, pipes, and similar building service equipment, without fire protection, penetrating a fire barrier. This occurs in the following areas: First Floor - Room 112; Basement - Room 005, 008, 015, 071, and 053. This is not compliant with NFPA 101 Section Life Safety Fire Barrier: Unprotected Penetrations (Legacy) Poor Percent Complete 0.0 Recommendation Seal openings with approved through-penetration firestopping system. Adjustment factor of 1.2 used to account for additional costs typically associated with retrofit work, and/or working with existing construction. Estimated Cost 4, Estimated Remaining Cost: 4, Action Date 12/1/ PAGE 61

62 Text6 L E G A C Y A S S E S S M E N T D A T A : R E Q Date Inspected 6/17/2005 Description There exists a required exit stair, Stair 4, that discharges through areas on the level of exit discharge. This is not compliant with NFPA 101 Section Requirement Category Requirement Name Condition Life Safety Means of Egress: Discharge from Exits (Legacy) Poor Percent Complete 0.0 Recommendation Install 1-hour fire rated partitons from Stair 4 to the northwest exit discharge by installing corridor from Vestibule 108B, through Room 104A, and into Room 103. Install 6'x7', 1-hour fire rated door assemblies with electronic hold-open devices to Vestibule 108B and Room 103. Installing corridor through Room 104A may require rearrangement of mechanical equipment. Adjustment factor of 1.6 used to account for additional costs typically associated with retrofit work, working with existing construction, and significant unknowns/variables due to complexity. Estimated Cost 39, Estimated Remaining Cost: 39, Action Date 6/17/2006 Text6 L E G A C Y A S S E S S M E N T D A T A : R E Q Date Inspected 6/17/2005 Description Requirement Category Requirement Name Condition Stair 4 and 5 continue past the level of exit discharge down to the basement and is required by NFPA 101 Section to be interrupted at the level of exit discharge. Life Safety Means of Egress: Interruption of Exit Stair (Legacy) Poor Percent Complete 0.0 Recommendation Install gate in both Stair 4 and 5 to separate the stair and prevent occupants from upper floors from continuing past the level of exit discharge. Adjustment factor of 2.0 used to account for additional costs typically associated with retrofit work, working with existing construction, limited-access conditions, and/or smaller size jobs (less than $5,000). Estimated Cost 16, Estimated Remaining Cost: 16, Action Date 6/17/ PAGE 62

63 Text6 L E G A C Y A S S E S S M E N T D A T A : R E Q Date Inspected 6/17/2005 Description The occupant load exceeds the total capacity of the means of egress for the basement floor. This is not compliant with NFPA 101 Section Requirement Category Requirement Name Condition Life Safety Means of Egress: Capacity (Legacy) Poor Percent Complete 0.0 Recommendation Install an outside stair from Room 074 on the east exterior wall with exit discharge at grade. Estimate includes construction of new stair from basement to grade. Adjustment factor of 1.6 used to account for additional costs typically associated with retrofit work, working with existing construction, and significant unknowns/variables due to complexity. Estimated Cost 27, Estimated Remaining Cost: 27, Action Date 6/17/2006 Text6 L E G A C Y A S S E S S M E N T D A T A : R E Q Date Inspected 6/17/2005 Description Stair 1 is a required exit that is an unenclosed stair. This is not compliant with NFPA 101 Section Requirement Category Requirement Name Condition Life Safety Means of Egress: Stair Enclosure (Legacy) Poor Percent Complete 0.0 Recommendation Stair 1: First Floor - Install a 1-hour partition and ceiling with a 6'x7', 1-hour fire rated door assembly (with electronic door closers). Adjustment factor of 1.6 used to account for additional costs typically associated with retrofit work, working with existing construction, and significant unknowns/variables due to complexity. Estimated Cost 15, Estimated Remaining Cost: 15, Action Date 6/17/ PAGE 63

64 Text6 L E G A C Y A S S E S S M E N T D A T A : R E Q Date Inspected 6/17/2005 Description Requirement Category Requirement Name Condition The basement level of the building qualifies as an underground structure with an occupant load greater than 100 occupants. The basement currently is not provided with sprinkler protection as required by NFPA 101 Section Life Safety Underground Structure: No A/S (Legacy) Poor Percent Complete 0.0 Recommendation Sprinkler protection is required for the entire Basement Level and all areas traversed by occupants in traveling to the exit discharge. Cost for installing water service, ceiling tile replacement, fire pump, etc. is included in the cost for the system. Adjustment factor of 1.6 used to account for additional costs typically associated with retrofit work, working with existing construction, and to ensure cost is near expected cost of approximately $4 to $6 per sq.ft. Estimated Cost 345, Estimated Remaining Cost: 345, Action Date 6/17/2006 Text6 L E G A C Y A S S E S S M E N T D A T A : R E Q Date Inspected 6/17/2005 Description Requirement Category Requirement Name Condition There exists an atrium in the north area of the building (Kincaid Pavilion). This atrium is permitted based upon NFPA 101 Section if the entire building is protected with a sprinkler system. Currently, only the basement is partially sprinklered. Life Safety Vertical Openings: Atrium (Legacy) Poor Percent Complete 0.0 Recommendation Install sprinkler system in the first and second floor (basement requires sprinklering in requirement "Underground Structure"). The cost includes installing water service, fire pump, etc. is included in the action for the requirement "Underground Structure". Adjustment factor of 1.6 used to account for additional costs typically associated with retrofit work, working with existing construction, and to ensure cost is near expected cost of approximately $4 to $6 per sq.ft. Estimated Cost 271, Estimated Remaining Cost: 271, Action Date 6/17/ PAGE 64

65 PAGE 65

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 4/19/2013 BUILDING SURVEY DATE

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 4/19/2013 BUILDING SURVEY DATE 0134 614 EAST PENNSYLVANIA AVENUE CHAMPAIGN, ILLINOIS 61820 SYSTEM CONDITION INDEX.528 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 495,100 LABORATORY BUILDING GROSS SQUARE

More information

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 6/5/2013 BUILDING SURVEY DATE

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 6/5/2013 BUILDING SURVEY DATE 0062 1105 WEST NEVADA STREET URBANA, ILLINOIS 61801 SYSTEM CONDITION INDEX.850 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 2,286,000 LABORATORY BUILDING GROSS SQUARE FEET

More information

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 6/4/2013 BUILDING SURVEY DATE

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 6/4/2013 BUILDING SURVEY DATE 0218 504 EAST ARMORY AVENUE CHAMPAIGN, ILLINOIS 61820 SYSTEM CONDITION INDEX.764 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 1,714,300 OFFICE BUILDING GROSS SQUARE FEET

More information

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 6/19/2013 BUILDING SURVEY DATE

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 6/19/2013 BUILDING SURVEY DATE 0154 52 EAST GREGORY DRIVE CHAMPAIGN, ILLINOIS 61820 SYSTEM CONDITION INDEX.646 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 1,203,500 OFFICE BUILDING GROSS SQUARE FEET

More information

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 6/6/2013 BUILDING SURVEY DATE

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 6/6/2013 BUILDING SURVEY DATE 0002 1301 SOUTH GOODWIN AVENUE URBANA, ILLINOIS 61801 SYSTEM CONDITION INDEX.862 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 746,400 CLASSROOMS / LIBRARY BUILDING GROSS

More information

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 4/11/2013 BUILDING SURVEY DATE

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 4/11/2013 BUILDING SURVEY DATE 0040 1402 WEST PENNSYLVANIA AVENUE URBANA, ILLINOIS 61801 SYSTEM CONDITION INDEX.685 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 1,364,800 LECTURE HALL BUILDING GROSS SQUARE

More information

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 6/6/2013 BUILDING SURVEY DATE

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 6/6/2013 BUILDING SURVEY DATE 0004 1103 SOUTH SIXTH STREET CHAMPAIGN, ILLINOIS 61820 SYSTEM CONDITION INDEX.810 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 1,831,000 CLASSROOMS / LIBRARY BUILDING GROSS

More information

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 6/18/2013 BUILDING SURVEY DATE

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 6/18/2013 BUILDING SURVEY DATE 0358 1004 SOUTH FOURTH STREET CHAMPAIGN, ILLINOIS 61820 SYSTEM CONDITION INDEX.508 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 2,281,700 CLASSROOMS / LIBRARY BUILDING GROSS

More information

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 6/6/2013 BUILDING SURVEY DATE

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 6/6/2013 BUILDING SURVEY DATE 0222 54 EAST GREGORY DRIVE CHAMPAIGN, ILLINOIS 61820 SYSTEM CONDITION INDEX.722 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 3,473,300 DISTRIBUTION BUILDING GROSS SQUARE

More information

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 02/08/2013 BUILDING SURVEY DATE

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 02/08/2013 BUILDING SURVEY DATE 0171 1503 SOUTH MARYLAND DRIVE URBANA, ILLINOIS 61801 SYSTEM CONDITION INDEX.770 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 2,686,100 LABORATORY BUILDING GROSS SQUARE

More information

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 6/3/2013 BUILDING SURVEY DATE

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 6/3/2013 BUILDING SURVEY DATE 0006 505 EAST AVENUE CHAMPAIGN, ILLINOIS 61820 SYSTEM CONDITION INDEX.492 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 10,114,300 BUILDING GROSS SQUARE FEET 260,748 NUMBER

More information

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 4/17/2013 BUILDING SURVEY DATE

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 4/17/2013 BUILDING SURVEY DATE 0039 1114 WEST NEVADA STREET URBANA, ILLINOIS 61801 SYSTEM CONDITION INDEX.766 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 9,578,600 CLASSROOMS / LIBRARY BUILDING GROSS

More information

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 2/15/2013 BUILDING SURVEY DATE

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 2/15/2013 BUILDING SURVEY DATE 0807 3502 SOUTH FIRST STREET CHAMPAIGN, ILLINOIS SYSTEM CONDITION INDEX.771 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 347,400 LABORATORY BUILDING GROSS SQUARE FEET 16,986

More information

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 2/6/2013 BUILDING SURVEY DATE

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 2/6/2013 BUILDING SURVEY DATE 0133 608 EAST PENNSYLVANIA AVENUE CHAMPAIGN, ILLINOIS 61820 SYSTEM CONDITION INDEX.516 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 646,900 PARKING STRUCTURE BUILDING GROSS

More information

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 4/10/2013 BUILDING SURVEY DATE

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 4/10/2013 BUILDING SURVEY DATE 0110 23 EAST STADIUM DRIVE CHAMPAIGN, ILLINOIS 61820 SYSTEM CONDITION INDEX.838 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 3,161,900 LABORATORY BUILDING GROSS SQUARE FEET

More information

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 2/4/2013 BUILDING SURVEY DATE

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 2/4/2013 BUILDING SURVEY DATE 0156 504 EAST PENNSYLVANIA AVENUE CHAMPAIGN, ILLINOIS 61820 SYSTEM CONDITION INDEX.461 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 16,618,500 CLASSROOMS / LIBRARY BUILDING

More information

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 6/18/2013 BUILDING SURVEY DATE

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 6/18/2013 BUILDING SURVEY DATE 0238 URBANA, ILLINOIS 61801 SYSTEM CONDITION INDEX.183 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 1,237,600 OFFICE BUILDING GROSS SQUARE FEET 18,054 NUMBER OF BUILDING

More information

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 2/13/2013 BUILDING SURVEY DATE

ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 2/13/2013 BUILDING SURVEY DATE 0197 1102 SOUTH GOODWIN AVENUE URBANA, ILLINOIS 61801 SYSTEM CONDITION INDEX.644 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 11,554,400 LABORATORY BUILDING GROSS SQUARE

More information

Listing of Events Fort McMurray Roman Catholic Seperate School District Fr. M. Beauregard School

Listing of Events Fort McMurray Roman Catholic Seperate School District Fr. M. Beauregard School Fort McMurray Roman Catholic Seperate School District Fr. M. Beauregard School Building Events 2004 2005 2006 2007 2008 Total Code Repair Add ventilation to storage room $ 1,000.00 $ - $ - $ - $ - $ 1,000.00

More information

Anson County Early College High

Anson County Early College High NC School District/040 Anson County/High School Anson County Early College High Final Campus Assessment Report March 11, 2017 PARSONS Campus Assessment Report Table of Contents Campus Executive Summary

More information

NC School District/520 Jones County/Elementary School Trenton Elementary Final Campus Assessment Report March 11, 2017

NC School District/520 Jones County/Elementary School Trenton Elementary Final Campus Assessment Report March 11, 2017 NC School District/520 Jones County/Elementary School Trenton Elementary Final Campus Assessment Report March 11, 2017 PARSONS Campus Assessment Report Table of Contents Campus Executive Summary 4 Campus

More information

Subject: Capital Reserve Expenditure Guidelines. *incl. former OCHAP/CSHP Peel Access to Housing (PATH)

Subject: Capital Reserve Expenditure Guidelines. *incl. former OCHAP/CSHP Peel Access to Housing (PATH) HIP Housing In Peel Subject: Capital Reserve Expenditure Guidelines Date: August 1, 2012 Applicable To The information contained in this document applies to the following: Municipal & Private Non- Federal

More information

Harnett Central High

Harnett Central High NC School District/430 Harnett County/High School Harnett Central High Final Campus Assessment Report March 11, 2017 PARSONS Campus Assessment Report Table of Contents Campus Executive Summary 6 Campus

More information

NC School District/430 Harnett County/Middle School Highland Middle Final Campus Assessment Report March 11, 2017

NC School District/430 Harnett County/Middle School Highland Middle Final Campus Assessment Report March 11, 2017 NC School District/430 Harnett County/Middle School Highland Middle Final Campus Assessment Report March 11, 2017 PARSONS Campus Assessment Report Table of Contents Campus Executive Summary 5 Campus Dashboard

More information

Davie County Early College High

Davie County Early College High NC School District/300 Davie County/High School Davie County Early College High Final Campus Assessment Report March 10, 2017 PARSONS Campus Assessment Report Table of Contents Campus Executive Summary

More information

Pleasantdale Elementary

Pleasantdale Elementary DeKalb County School District/Elementary Schools Pleasantdale Elementary Final School Assessment Report May 20, 2016 PARSONS School Assessment Report Table of Contents School Executive Summary 5 School

More information

BUILDING PERMIT FEES

BUILDING PERMIT FEES BUILDING PERMIT FEES 1. Building Permit Fee Based on the Construction Valuation of the project excluding site work. Refer to Fee Charts below. Electrical, Mechanical and Plumbing permits are not included

More information

Bob Mathis Elementary

Bob Mathis Elementary DeKalb County School District/Elementary Schools Bob Mathis Elementary Final School Assessment Report May 19, 2016 PARSONS School Assessment Report Table of Contents School Executive Summary 4 School Condition

More information

Mountain Heritage High

Mountain Heritage High NC School District/995 Yancey County/High School Mountain Heritage High Final Campus Assessment Report March 12, 2017 PARSONS Campus Assessment Report Table of Contents Campus Executive Summary 7 Campus

More information

Sagamore Hills Elementary

Sagamore Hills Elementary DeKalb County School District/Elementary Schools Sagamore Hills Elementary Final School Assessment Report May 20, 2016 PARSONS School Assessment Report Table of Contents School Executive Summary 4 School

More information

Anderson Creek Primary

Anderson Creek Primary NC School District/430 Harnett County/Elementary School Anderson Creek Primary Final Campus Assessment Report March 11, 2017 PARSONS Campus Assessment Report Table of Contents Campus Executive Summary

More information

Washingtonville Central School District Building Condition Survey Five Year Plan

Washingtonville Central School District Building Condition Survey Five Year Plan Building Condition Survey Five Year Plan Project Cost Summary Building 2011 2012 2013 2014 2015 Totals 0001 Washingtonville Jr High School $38,759 $325,990 $1,882,653 $1,417,341 $1,025,559 $4,690,302 0002

More information

Laurel Hill Elementary

Laurel Hill Elementary NC School District/830 Scotland County/Elementary School Laurel Hill Elementary Final Campus Assessment Report March 11, 2017 PARSONS Campus Assessment Report Table of Contents Campus Executive Summary

More information

NC School District/430 Harnett County/Elementary School Gentry Primary Final Campus Assessment Report March 11, 2017

NC School District/430 Harnett County/Elementary School Gentry Primary Final Campus Assessment Report March 11, 2017 NC School District/430 Harnett County/Elementary School Gentry Primary Final Campus Assessment Report March 11, 2017 PARSONS Campus Assessment Report Table of Contents Campus Executive Summary 6 Campus

More information

Pinebrook Elementary

Pinebrook Elementary NC School District/300 Davie County/Elementary School Pinebrook Elementary Final Campus Assessment Report March 10, 2017 PARSONS Campus Assessment Report Table of Contents Campus Executive Summary 6 Campus

More information

Educational & Performing Arts Center: Downriver Campus

Educational & Performing Arts Center: Downriver Campus Educational & Performing Arts Center: Total Estimated Project Construction Cost: $ 18.04 million Groundbreaking: September 2006 Percentage Completed: 100 percent Anticipated Completion Date: Completed

More information

Central Davie Academy

Central Davie Academy NC School District/300 Davie County/High School Central Davie Academy Final Campus Assessment Report March 10, 2017 PARSONS Campus Assessment Report Table of Contents Campus Executive Summary 4 Campus

More information

Stone Mountain Middle

Stone Mountain Middle DeKalb County School District/Middle Schools Stone Mountain Middle Final School Assessment Report May 20, 2016 PARSONS School Assessment Report Table of Contents School Executive Summary 4 School Condition

More information

Harnett Central Middle

Harnett Central Middle NC School District/430 Harnett County/Middle School Harnett Central Middle Final Campus Assessment Report March 11, 2017 PARSONS Campus Assessment Report Table of Contents Campus Executive Summary 5 Campus

More information

DeKalb Elementary School of the Arts at Terry Mills

DeKalb Elementary School of the Arts at Terry Mills DeKalb County School District/Elementary Schools DeKalb Elementary School of the Arts at Terry Mills Final School Assessment Report May 19, 2016 PARSONS School Assessment Report Table of Contents School

More information

Lafayette Elementary

Lafayette Elementary NC School District/430 Harnett County/Elementary School Lafayette Elementary Final Campus Assessment Report March 11, 2017 PARSONS Campus Assessment Report Table of Contents Campus Executive Summary 5

More information

Howsyth Court Condominium Corporation No. CCN Avenue SW Calgary, Alberta

Howsyth Court Condominium Corporation No. CCN Avenue SW Calgary, Alberta Entuitive Corporation Calgary + Toronto Howsyth Court Condominium Corporation No. CCN9011190 305 25 Avenue SW Calgary, Alberta Submitted By: Entuitive Corporation 209 8 th Avenue SW, Suite 300 Calgary,

More information

City School District of Albany Five Year Facilities Plan 3/14/2019

City School District of Albany Five Year Facilities Plan 3/14/2019 Bold indicates change from 3/7/19 BOE meeting Available Local Share $ 3,300,000 1 SPA Air condition gymnasium $ 267,000 1 $ 41,385 $ 41,385 $ 267,000 2 DCS Air condition gymnasium $ 221,000 1 $ 34,255

More information

DeKalb County School District/High Schools Druid Hills High Final School Assessment Report May 19, 2016

DeKalb County School District/High Schools Druid Hills High Final School Assessment Report May 19, 2016 DeKalb County School District/High Schools Druid Hills High Final School Assessment Report May 19, 2016 PARSONS School Assessment Report Table of Contents School Executive Summary 5 School Condition Summary

More information

Northern Gateway Regional Division No.10 Listing of Events

Northern Gateway Regional Division No.10 Listing of Events Building Events Maintenance Events D2020.01.03 Piping Specialties (Backflow Preventors)** David Ovans Elementary School B3989A Code Northern Gateway Regional Division No.10 Install vacuum breakers on non

More information

Lilesville Elementary

Lilesville Elementary NC School District/040 Anson County/Elementary School Lilesville Elementary Final Campus Assessment Report March 11, 2017 PARSONS Campus Assessment Report Table of Contents Campus Executive Summary 4 Campus

More information

Robert Shaw Theme Elementary

Robert Shaw Theme Elementary DeKalb County School District/Elementary Schools Robert Shaw Theme Elementary Final School Assessment Report May 20, 2016 PARSONS School Assessment Report Table of Contents School Executive Summary 4 School

More information

Our Focus: Your Future

Our Focus: Your Future Town of Fort Erie Infrastructure Services Our Focus: Your Future Prepared for Council-in-Committee Report No. IS-53-07 Agenda Date November 19, 2007 File No. 220102 Subject 5 YEAR FACILITY CONDITION STATUS

More information

William Bradley Bryant Center

William Bradley Bryant Center DeKalb County School District/Education Other William Bradley Bryant Center Final School Assessment Report May 19, 2016 PARSONS School Assessment Report Table of Contents School Executive Summary 4 School

More information

DeKalb County School District/Elementary Schools Dunwoody Elementary Final School Assessment Report May 19, 2016

DeKalb County School District/Elementary Schools Dunwoody Elementary Final School Assessment Report May 19, 2016 DeKalb County School District/Elementary Schools Dunwoody Elementary Final School Assessment Report May 19, 2016 PARSONS School Assessment Report Table of Contents School Executive Summary 4 School Condition

More information

Questions by Vendors: District Answers are in Red. Vendor Questions are in Black.

Questions by Vendors: District Answers are in Red. Vendor Questions are in Black. Questions by Vendors: District Answers are in Red. Vendor Questions are in Black. 1. Can we receive a final Excel Sheet of all Facilities that includes physical addresses, square foot info and original

More information

BUILDING SUBCODE FEES:

BUILDING SUBCODE FEES: Building Sub-code PERMIT FEES TOWNSHIP OF PENNSVILLE 2011 (A 4-2011) 1. Plan review shall be 20% of the amount to be charged for a construction permit. a. The fee for plan review for elevator devices in

More information

Ronald E. McNair Discovery Learning Academy

Ronald E. McNair Discovery Learning Academy DeKalb County School District/Elementary Schools Ronald E. McNair Discovery Learning Academy Final School Assessment Report May 20, 2016 PARSONS School Assessment Report Table of Contents School Executive

More information

TOWNSHIP OF FRANKLIN O-6-18 ORDINANCE AMENDING CHAPTER OF THE CODE OF THE TOWNSHIP OF FRANKLIN- CONSTRUCTION PERMITS

TOWNSHIP OF FRANKLIN O-6-18 ORDINANCE AMENDING CHAPTER OF THE CODE OF THE TOWNSHIP OF FRANKLIN- CONSTRUCTION PERMITS TOWNSHIP OF FRANKLIN O-6-18 ORDINANCE AMENDING CHAPTER 190-2 OF THE CODE OF THE TOWNSHIP OF FRANKLIN- CONSTRUCTION PERMITS WHEREAS, it is the desire of the Township Committee of the Township of Franklin,

More information

BUILDING CONDITION ASSESSMENT. A Comprehensive Approach in Energy and Facility Management

BUILDING CONDITION ASSESSMENT. A Comprehensive Approach in Energy and Facility Management BUILDING CONDITION ASSESSMENT A Comprehensive Approach in Energy and Facility Management Presentation Outline Page Nadine International Company Profile.. 3 FCI -Industry Preferred Formula.... 4 FCI -Other

More information

What did they tell me?

What did they tell me? LBS Insurance Commission Oct 25, 2018 What did they tell me? Handouts from the October 25, 2018 Insurance Town Hall C R. Reynolds 1 High Level Recap of Changes for 2018-19 Deductible $5,000 -> $25,000

More information

Building Division Fees 2018

Building Division Fees 2018 Building Division Fees 2018 Permit Administration A permit administration fee of $45.00 shall be assessed for each permit. Staff Consultation Fee $75.00 Administration Determination $90.00 / hour; $23.00

More information

Backlog Reduction Plan

Backlog Reduction Plan 2003-2013 Executive Summary proposes to achieve reductions in our facilities maintenance backlog by documenting and completing backlog projects on a priority basis and by minimizing or eliminating future

More information

Facility Condition Assessment. Facility Condition Assessment 8/13/2013 AGENDA

Facility Condition Assessment. Facility Condition Assessment 8/13/2013 AGENDA AGENDA benefits & limitations Rod Moore, RA, LEED AP, PMP Georgia Tech Benjamin Dutton, FFB, MCIOB, MRICS Faithful+Gould GT Facilities GT Program What is GT FCA Deliverables How GT uses FCA Information

More information

Reference: The Bel-Harbour Condominium Association Reserve Study Update Kipcon Great Lakes Project No CRU

Reference: The Bel-Harbour Condominium Association Reserve Study Update Kipcon Great Lakes Project No CRU August 18, 2016 Mr. Nicholas Burbulis 420 W. Belmont Ave. Chicago, IL 60657 Reference: The Kipcon Great Lakes Dear Mr. Burbulis: Attached, please find Kipcon Great Lakes, which has been prepared for the.

More information

Social Housing Administration Directive No

Social Housing Administration Directive No Regional Municipality of Halton Social Housing Administration Directive No. 06-05 Date: August 30, 06 To: Federally-Funded Social Housing Providers subject to Operating Agreements under Section 95 of the

More information

Mocksville Elementary

Mocksville Elementary NC School District/300 Davie County/Elementary School Mocksville Elementary Final Campus Assessment Report March 10, 2017 PARSONS Campus Assessment Report Table of Contents Campus Executive Summary 5 Campus

More information

Urban Heights Condominium

Urban Heights Condominium Condominium Capital 2011 2010, AssociationAnalysis, LLC Condominium Prepared For: Table of Contents Condominium Association, Inc. 1642 Maxwell Road Atlanta, GA 30012 October 19, 2010 INTRODUCTION INTRODUCTION

More information

William Ellis Middle

William Ellis Middle NC School District/300 Davie County/Middle School William Ellis Middle Final Campus Assessment Report March 10, 2017 PARSONS Campus Assessment Report Table of Contents Campus Executive Summary 5 Campus

More information

NC School District/430 Harnett County/Elementary School Coats Elementary Final Campus Assessment Report March 11, 2017

NC School District/430 Harnett County/Elementary School Coats Elementary Final Campus Assessment Report March 11, 2017 NC School District/430 Harnett County/Elementary School Coats Elementary Final Campus Assessment Report March 11, 2017 PARSONS Campus Assessment Report Table of Contents Campus Executive Summary 5 Campus

More information

Martin Luther King Jr. High

Martin Luther King Jr. High DeKalb County School District/High Schools Martin Luther King Jr. High Final School Assessment Report May 19, 2016 PARSONS School Assessment Report Table of Contents School Executive Summary 4 School Condition

More information

CAPITAL RESERVE FUNDING ANALYSIS

CAPITAL RESERVE FUNDING ANALYSIS CAPITAL RESERVE FUNDING ANALYSIS FOR BROADWAY HOUSING, LLC 625 SW Jackson Portland, OR Prepared by: Capital Reserve Consultants, LLC Carson M. Horton, RS April 2014 Copyright 2014 USA / Canada 503 336

More information

Hayfield Community Schools Bond Referendum. Vote Monday, September 11, Our Schools Our Communities Our Future

Hayfield Community Schools Bond Referendum. Vote Monday, September 11, Our Schools Our Communities Our Future Hayfield Community Schools 2017 Bond Referendum Vote Monday, September 11, 2017 Our Schools Our Communities Our Future 2017 Bond Referendum What s Already Been Done? Studies and Meetings and Meetings 2014-15

More information

Marion County Marion Public County Works Public Building Works Inspection Division

Marion County Marion Public County Works Public Building Works Inspection Division FEE SCHEDULE The final determination of valuation, occupancy, and/or construction type under any of the provisions of this order shall be made by the Building Official. A. Structural Permits: The valuation

More information

Protecting your older home

Protecting your older home Protecting your older home HOMEOWNERS INSURANCE Helping you protect your biggest investment: your home At Travelers, we care about our homeowners. We want you to get the most out of the older home you

More information

1. The fee for plan review shall be due upon completion of subcode review.

1. The fee for plan review shall be due upon completion of subcode review. New Jersey State permit surcharge fees: Amount: This fee shall be in the amount of $0.00334 per cubic foot volume of new buildings and additions. Volume shall be computed in accordance with N.J.A.C. 5:232.28.

More information

All electrical, gas and plumbing applications, together with the fee amount, must be mailed or delivered to:

All electrical, gas and plumbing applications, together with the fee amount, must be mailed or delivered to: Application for Permit to Perform Electrical Work Massachusetts Uniform Application for a Permit to do Gas Fitting Massachusetts Uniform Application for a Permit to Perform Plumbing Work Applications and

More information

Greenbelt Homes, Inc Budget

Greenbelt Homes, Inc Budget Greenbelt Homes, Inc. 2015 Budget October 9, 2014 First Presentation Finance/Board of Directors November 6, 2014 First Reading November 20, 2014 Second Reading and Approval November 20, 2014 Second Reading

More information

One and two family residences... $ Mobile Homes... $73.73 Commercial Building... $ All other miscellaneous applications... $44.

One and two family residences... $ Mobile Homes... $73.73 Commercial Building... $ All other miscellaneous applications... $44. EXHIBIT "A" BUILDING PERMITS, HOUSING CODE AND MOBILE HOME PERMIT FEES Page 1 of 9 I. APPLICATION FEES (Non-refundable) One and two family residences... $147.59 Mobile Homes... $73.73 Commercial Building...

More information

FOR APARTMENTS SEGMENT

FOR APARTMENTS SEGMENT UNDERWRITING GUIDELINES FOR APARTMENTS SEGMENT Local exceptions to these underwriting guidelines may apply. Please consult with your underwriter or sales executive for details and to discuss risks which

More information

NUNAVUT HOUSING CORPORATION. Home Renovation Program (HRP)

NUNAVUT HOUSING CORPORATION. Home Renovation Program (HRP) NUNAVUT HOUSING CORPORATION Home Renovation (HRP) October 2014 Date October 201 TABLE OF CONTENTS OBJECTIVE... 1 SUMMARY... 1 ENABLING LEGISLATION... 1 ELIGIBLE CLIENTS... 1 PRIORITY OF APPLICANTS...

More information

Yakima County Code ~ Building and Construction ~ Title FEES

Yakima County Code ~ Building and Construction ~ Title FEES 13.24.010 AMENDED FEE TABLES AND FEE SCHEDULES The fee tables and fee schedules contained in the various codes and regulations adopted in this title shall be amended as established herein. *PLAN REVIEW

More information

CITY OF TAMARAC BUILDING DEPARTMENT Schedule of Permit Fees

CITY OF TAMARAC BUILDING DEPARTMENT Schedule of Permit Fees CITY OF TAMARAC BUILDING DEPARTMENT Schedule of Permit Fees SECTION I: As set forth in Section 105 of the Broward County Amendments to the 5th Edition (2014) Florida Building Code, it is unlawful for any

More information

Condominium. Travelers Condominium Pac SM and Condominium Pac Plus SM are designed for owners of buildings used exclusively as condominiums.

Condominium. Travelers Condominium Pac SM and Condominium Pac Plus SM are designed for owners of buildings used exclusively as condominiums. 25 Condominium Travelers Condominium Pac SM and Condominium Pac Plus SM are designed for owners of buildings used exclusively as condominiums. Eligibility Up to $10 million Total Insured Values per building,

More information

June 15, City Of Rochelle 420 N 6th St Rochelle, IL Att: Ms. Sue Messer. UPDATED: Old Building / HVAC Controls and Energy Improvements

June 15, City Of Rochelle 420 N 6th St Rochelle, IL Att: Ms. Sue Messer. UPDATED: Old Building / HVAC Controls and Energy Improvements City Of Rochelle 420 N 6th St Rochelle, IL 61068 Att: Ms. Sue Messer June 15, 2018 Helm Group Mechanical Inc Advanced Automation Solutions Group 2279 Route 20 East Freeport, Illinois 61032 UPDATED: Old

More information

Best Practices Dealing With Vacant, Idle, Or Shut-Down Facilities

Best Practices Dealing With Vacant, Idle, Or Shut-Down Facilities Global Asset Protection Services Best Practices Dealing With Vacant, Idle, Or Shut-Down Facilities By: Sobhy Girgis XL GAPS June 2011 Background Anticipating the Vacancies 85% to 90% of the time advance

More information

REPLACEMENT RESERVE GUIDE

REPLACEMENT RESERVE GUIDE CANADA MORTGAGE AND HOUSING CORPORATION REPLACEMENT RESERVE GUIDE What is the Replacement Reserve? The replacement reserve is a fund kept by each housing sponsor under the terms of its operating agreement

More information

TABLE OF CONTENTS - ADDENDUM NO. 3

TABLE OF CONTENTS - ADDENDUM NO. 3 TABLE OF CONTENTS - ADDENDUM NO. 3 TABLE OF CONTENTS Addendum No. 3 SUPPLEMENTAL INSTRUCTIONS TO BIDDERS SIB-1 SIB-2 SIB-3 Article I-2.4 - Contract Completion Time Article I-14.4 - Participation by SBE

More information

CONVENIENCE STORE QUICK APPLICATION WITH AND WITHOUT GAS PUMPS

CONVENIENCE STORE QUICK APPLICATION WITH AND WITHOUT GAS PUMPS CONVENIENCE STORE QUICK APPLICATION WITH AND WITHOUT GAS PUMPS Binding subject to any additional information when required by IIC. Agency Agency Contact Email: Effective Date Expiration Date: Years in

More information

Hyde Park Place Owners' Association, Inc.

Hyde Park Place Owners' Association, Inc. RESERVE STUDY Full Study Hyde Park Place Owners' Association, Inc. Published - February 10, 2016 Browning Reserve Group / Emmett, ID 83617 Office (208) 365-0977 Tony@BrowningRG.com / www.browningrg.com

More information

Physical Plant. Five-Year Capital Budget Plan. State College Area School District November Page 1 of 15

Physical Plant. Five-Year Capital Budget Plan. State College Area School District November Page 1 of 15 Physical Plant Five-Year Capital Budget Plan State College Area School District November 2011 Page 1 of 15 Table of Contents Background and 2013 Projects Pages 3-5 Funding Level Pages 6-7 Existing Buildings

More information

CIP FY2015 FY2019 Requests SCH-1, SCH-2 and SCH-5

CIP FY2015 FY2019 Requests SCH-1, SCH-2 and SCH-5 CIP FY2015 FY2019 Requests SCH-1, SCH-2 and SCH-5 Edwin Ataide Deputy Director Plant & Facilities SCH-1 School Projects All Schools Priority FY15 FY16 FY17 FY18 FY19 ADA Compliance (Handicap Accessibility)

More information

DEPRECIATION REPORT Strata VR 1591 The Leicester West 13th Avenue Vancouver BC V6J 2G5

DEPRECIATION REPORT Strata VR 1591 The Leicester West 13th Avenue Vancouver BC V6J 2G5 DEPRECIATION REPORT 2015 Strata VR 1591 The Leicester 1545 West 13th Avenue Vancouver BC V6J 2G5 Created by Strata Council Members Merry Meredith Tom Heise Antoine Issa The authors have compiled this report

More information

UNIVERSITY OF H OUSTON SYSTEM UNIVERSITY OF HOUSTON Facilities Planning and Construction

UNIVERSITY OF H OUSTON SYSTEM UNIVERSITY OF HOUSTON Facilities Planning and Construction UNIVERSITY OF H OUSTON SYSTEM UNIVERSITY OF HOUSTON Facilities Planning and Construction MPEC MEETING MINUTES Subject: Maintenance Project Evaluation Committee Attendees: Jeffrey Benjamin, George Rea,

More information

Fee Schedule for 2017

Fee Schedule for 2017 EXHIBIT A Fee Schedule for GENERAL CITY ADMINISTRATIVE FEES Business Licenses Neighborhood Business License Neighborhood Business License - Initial Application Neighborhood Business License - Annual Renewal

More information

Update With Site Visit

Update With Site Visit Update With Site Visit Le Chateau Bellevue, WA 10/28/2011 Report #1002 Phone: 253-241-8151 Fax: 360-872-8073 E-mail: jeremy@reservesolutions.net www.reservesolutions.net Le Chateau Client Info: REPORT

More information

Agenda Item # 5b Page 1 of 43

Agenda Item # 5b Page 1 of 43 Page 1 of 43 Page 2 of 43 Page 3 of 43 Page 4 of 43 Page 5 of 43 Page 6 of 43 Page 7 of 43 Page 8 of 43 Page 9 of 43 Page 10 of 43 Page 11 of 43 Page 12 of 43 Page 13 of 43 Page 14 of 43 Page 15 of 43

More information

Comprehensive Reserve Fund Study and Building Condition Assessment for Wellington Standard Condominium Corporation No. 149

Comprehensive Reserve Fund Study and Building Condition Assessment for Wellington Standard Condominium Corporation No. 149 Comprehensive Reserve Fund Study and Building Condition Assessment for Wellington Standard Condominium Corporation No. 149 820 Gartshore Street Fergus, Ontario Report Prepared for the Board of Directors

More information

Reserve Fund Study prepared for The Greens at Pelican Point Homeowners Association February 2013 prepared by

Reserve Fund Study prepared for The Greens at Pelican Point Homeowners Association February 2013 prepared by Reserve Fund Study prepared for The Greens at Pelican Point Homeowners Association February 2013 prepared by Craig Naden and John Carlson Table of Contents TABLE OF CONTENTS Page No. 1.0 EXECUTIVE SUMMARY...

More information

ATTIC FAN - DECEMBER 1995

ATTIC FAN - DECEMBER 1995 400 Ashley Court Glen Mills, PA 19342 Phone: 610-459-0510 Fax: 610-459-5317 ATTIC FAN - DECEMBER 1995 WHEREAS, the Declaration of Condominium for Darlington Woods Condominium restricts alterations of any

More information

Code Reference: Section , F.S. Chapter ; FS Section ; Responsible Dept.: Community Development/Building Division

Code Reference: Section , F.S. Chapter ; FS Section ; Responsible Dept.: Community Development/Building Division Building Construction Permit Fees 322100 Building Division 341910 Planning Division 341940 Harbor/Code Division 322200/322300 Surcharge Building Permit Fees The governing bodies of local governments may

More information

Overview of Public Schools CIP

Overview of Public Schools CIP Overview of Public Schools CIP The Public Schools Community Investment Plan (CIP) includes school construction, additions and modernizations, as well as other school related projects. For more than a decade

More information

FY17 FMD Capital Budget

FY17 FMD Capital Budget FY17 FMD Capital Budget School Committee Presentation December 2, 2015 Wellesley Facilities Maintenance Department AGENDA Status Update on Capital Projects Role in Capital Planning Capital Planning & Budgeting

More information

Georgetown Community Center Rental Information

Georgetown Community Center Rental Information Georgetown Community Center Rental Information The City of Georgetown welcomes you and thanks you for your consideration in renting our Community Center! We hope you and your family or group will enjoy

More information

Integrating Green Building Measures into Capital Planning for HUD Assisted and Public Housing Programs

Integrating Green Building Measures into Capital Planning for HUD Assisted and Public Housing Programs Building Bridges to Net Zero Integrating Green Building Measures into Capital Planning for HUD Assisted and Public Housing Programs Evolution of HUD's Green Capital Needs Assessment, and the new CNA etool

More information