ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 4/19/2013 BUILDING SURVEY DATE
|
|
- Jean Parsons
- 6 years ago
- Views:
Transcription
1 EAST PENNSYLVANIA AVENUE CHAMPAIGN, ILLINOIS SYSTEM CONDITION INDEX.528 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 495,100 LABORATORY BUILDING GROSS SQUARE FEET 10,528 NUMBER OF BUILDING STORIES 1 BUILDING SURVEY DATE CCJM: Josh Polasky (M), Stanley Panek (E) ORIGINAL YEAR OF CONSTRUCTION /19/2013 B U I L D I N G D I S C I P L I N E R E P L A C E M E N T C O S T S U M M A R Y TRADE E X P E C T E D R E M A I N I N G S E R V I C E L I F E FAIR ($) GOOD ($) (5-10 YEARS) (10-20 YEARS) POOR ($) (1-5 YEARS) EXCELLENT ($) (20+ YEARS) TOTAL ($) $/GSF PERCENT OF BUILDING TOTAL (%) MECHANICAL 74,000 80, , PLUMBING 52,300 52, FIRE PROTECTION 20,500 20, ELECTRICAL 114,500 35,000 80, , COMMUNICATIONS 38,300 38, TOTAL % OF TOTAL CRITICAL ITEM REMEDIATION COST: $107, , , , , REFER TO CRITICAL ITEM SUMMARY ON FOLLOWING PAGE. NOTE: Cost Estimates are Construction Costs are in 2013 dollars to Replace in Kind unless otherwise noted PAGE 1
2 N A T U R A L H I S T O R Y S U R V E Y G R E E N H O U S E C R I T I C A L I S S U E S S U M M A R Y SYSTEM/COMPONENT FAILURE ITEMS REPAIR COST REPLACEMENT COST REPAIR/ REPLACEMENT % REMAINING LIFE REPAIR OR REPLACE MECHANICAL Steam and Condensate System Numerous steam repairs are necessary, pipes are leaky, and 74,000 74, Exceeded Replace steam hammering is common. PLUMBING Storm and Subsoil Drainage There is a roof leak and basement flooding in the Head House; 32,000 32, Exceeded Replace these are possibly related. ELECTRICAL Lighting Control System Replacement of deteriorated time switches. 1,200 22, Exceeded Replace SYSTEM/COMPONENT FAILURE ITEMS COST 107, , CRITICAL ISSUES COST 107, , NOTE: Cost Estimates are Construction Costs are in 2013 dollars to remediate noted issue. Text106 M E C H A N I C A L D I S C I P L I N E R E P L A C E M E N T C O S T S U M M A R Y STEAM AND CONDENSTATE SYSTEM SUPPLY AIR SYSTEM HVAC CONTROLS SYSTEM SYSTEM/COMPONENT Steam and Condensate System Ventilation System HVAC Controls MECHANICAL TOTAL % OF TOTAL POOR (1-5 YEARS) E X P E C T E D R E M A I N I N G S E R V I C E L I F E FAIR (5-10 YEARS) GOOD (10-20 YEARS) EXCELLENT (20+ YEARS) TOTAL 74,000 74,000 76,000 76,000 4,300 4,300 74,000 80, , PAGE 2
3 Text6 S T E A M A N D C O N D E N S A T E S Y S T E M A S S E S S M E N T D A T A Description Overall Condition Item ID Date Installed 1/1/1942 Comments Critical Issues Critical Repair Estimate $74,000 Head House and Greenhouse are served by steam from the Natural Resources building. There is no condensate pump; condensate drains back to the Natural Resources Building. Steam serves radiators throughout Head House and Greenhouse. Poor Remaining Useful Life Exceeded Nominal Useful Life: 30 Years Replacement Cost $74,000 Staff reports steam radiators have difficulty maintaining a constant temperature. The high humidity in the Greenhouse (by design) has been highly corrosive to steel pipes and radiators. Numerous steam repairs are necessary, pipes are leaky, and steam hammering is common PAGE 3
4 Text6 S T E A M A N D C O N D E N S A T E S Y S T E M S U R V E Y P H O T O G R A P H S Radiator in Head House Radiator in Basement (loud steam hammering) Radiator in Greenhouse Steam Piping PAGE 4
5 Text6 V E N T I L A T I O N S Y S T E M A S S E S S M E N T D A T A Description Overall Condition Date Installed 1/1/1993 Recommendation Item ID Critical Issues Ventilation consists of 2 exhaust fans in Head House (poor condition, approx. 5 HP) and 16 evaporative cooling fans in the Greenhouse (fair/poor condition, unavailable HP, see pictures). Greenhouse window walls also open via hand crank. Fair Remaining Useful Life 10 Years Nominal Useful Life: 30 Years Replacement Cost $76,000 Check structural integrity of Greenhouse glass walls and roof. Wooden frame of greenhouse is extremely degraded and weak to the point where safety is questionable PAGE 5
6 Text6 V E N T I L A T I O N S Y S T E M S U R V E Y P H O T O G R A P H S Head House Exhaust Fan Evaporative Cooling Fans Evaporative Cooling Fans (interior) Wooden Greenhouse Framing PAGE 6
7 Text6 H V A C C O N T R O L S A S S E S S M E N T D A T A Item ID Description Small Quincy Overall Condition Fair Date Installed 1/1/2005 Remaining Useful Life 6 Years Nominal Useful Life: 18 Years Manufacturer Quincy Replacement Cost $4,300 Comments Small Quincy compressor system (2-3 HP, fair condition) serves pneumatic thermostats which serve steam radiators. Text6 H V A C C O N T R O L S S U R V E Y P H O T O G R A P H S Quincy Compressor System PAGE 7
8 Text106 P L U M B I N G D I S C I P L I N E R E P L A C E M E N T C O S T S U M M A R Y DOMESTIC HOT WATER SYSTEM SUB-SOIL DRAINAGE SYSTEM SYSTEM/COMPONENT Domestic Hot and Cold Water Storm and Subsoil Drainage PLUMBING TOTAL % OF TOTAL POOR (1-5 YEARS) E X P E C T E D R E M A I N I N G S E R V I C E L I F E FAIR GOOD (5-10 YEARS) (10-20 YEARS) EXCELLENT (20+ YEARS) TOTAL 20,300 20,300 32,000 32,000 52,300 52, PAGE 8
9 Text6 D O M E S T I C H O T A N D C O L D W A T E R A S S E S S M E N T D A T A Description Overall Condition Item ID Date Installed 1/1/1942 Comments Domestic water from the Natural Resources Building serves sinks, garden hoses, and plant irrigation throughout the Head House and Greenhouse portions of this building. There is no bathroom. There is one residential style water heater (Sears, Electric, gal, poor condition) serving a utility sink. Poor Remaining Useful Life Exceeded Nominal Useful Life: 50 Years Replacement Cost $20,300 This system is in very poor condition. The plant irrigation system is described as homemade PAGE 9
10 Text6 D O M E S T I C H O T A N D C O L D W A T E R S U R V E Y P H O T O G R A P H S Irrigation Pipes Utility Sink with Water Heater Garden Faucet Irrigation Pipes Under Plant Beds PAGE 10
11 Text6 S T O R M A N D S U B S O I L D R A I N A G E A S S E S S M E N T D A T A Item ID Description One sump pump located in Head House basement age unknown. Overall Condition Poor Date Installed 1/1/1942 Remaining Useful Life Exceeded Nominal Useful Life: 50 Years Recommendation Repair roof leak. Investigate source of basement flooding. Replacement Cost $32,000 Critical Issues There is a roof leak and basement flooding in the Head House; these are possibly related. Critical Repair Estimate $32,000 Text6 S T O R M A N D S U B S O I L D R A I N A G E S U R V E Y P H O T O G R A P H S Basement Sump Pump Basement Flooding in Head House Roof Leak in Head House PAGE 11
12 Text106 F I R E P R O T E C T I O N D I S C I P L I N E R E P L A C E M E N T C O S T S U M M A R Y FIRE ALARM SYSTEM SYSTEM/COMPONENT Fire Alarm System FIRE PROTECTION TOTAL % OF TOTAL POOR (1-5 YEARS) E X P E C T E D R E M A I N I N G S E R V I C E L I F E FAIR GOOD (5-10 YEARS) (10-20 YEARS) EXCELLENT (20+ YEARS) TOTAL 20,500 20,500 20,500 20, PAGE 12
13 Text6 F I R E A L A R M S Y S T E M A S S E S S M E N T D A T A Item ID Description Fire alarm includes pull stations and heat detectors. System is connected to fire alarm panel located in Natural History Building Overall Condition Poor Date Installed 1/1/1989 Remaining Useful Life Exceeded Nominal Useful Life: 20 Years Equipment Tag - Manufacturer Pyrotronics Model Number XL 3 Serial Number - Size/Capacity - HP/kW - Voltage - Material - Recommendation - Replacement Cost $20, PAGE 13
14 Text6 F I R E A L A R M S Y S T E M S U R V E Y P H O T O G R A P H S Fire alarm pull station Fire Alarm heat detector PAGE 14
15 Text106 E L E C T R I C A L D I S C I P L I N E R E P L A C E M E N T C O S T S U M M A R Y LOW VOLTAGE SYSTEM EMERGENCY POWER SYSTEM INTERIOR LIGHTING EMERGENCY LIGHTING SYSTEM EXIT LIGHTING SYSTEM LIGHTING CONTROL SYSTEM EXTERIOR LIGHTING SYSTEM SYSTEM/COMPONENT Low Voltage Distribution System Emergency Power System Interior Lighting-Greenhouse Interior Lighting-Head house Emergency Lighting System Exit Lighting System Lighting Control System Exterior Lighting ELECTRICAL TOTAL % OF TOTAL POOR (1-5 YEARS) E X P E C T E D R E M A I N I N G S E R V I C E L I F E FAIR GOOD (5-10 YEARS) (10-20 YEARS) EXCELLENT (20+ YEARS) TOTAL 80,100 80,100 35,000 35,000 56,000 56,000 13,100 13,100 3,100 3,100 5,900 5,900 22,700 22,700 13,800 13, ,500 35,000 80, , PAGE 15
16 Text6 L O W V O L T A G E D I S T R I B U T I O N S Y S T E M A S S E S S M E N T D A T A Description Overall Condition Item ID Date Installed 1/1/1993 Equipment Tag - Manufacturer Model Number - HP/kW - Material - Comments Critical Issues Low voltage distribution includes main distribution panelboard and (2) lighting/power panelboards.power for Greenhouse originates at switchboard CA located in Natural History Building. Chiller serving Natural History Building receives power from Greenhouse distribution panelboard. Good Remaining Useful Life 20 Years Nominal Useful Life: 40 Years Serial Number - Size/Capacity Voltage Recommendation - Westinghouse 400 A 120/208 V Replacement Cost $80,100 Wiring in greenhouse area is deteriorating due to moisture and age. Installation of ground fault protection for outlets in wet areas PAGE 16
17 Text6 L O W V O L T A G E D I S T R I B U T I O N S Y S T E M S U R V E Y P H O T O G R A P H S Branch panelboard Distribution panelboard Lighting panelboard Distribution panelboard name plate PAGE 17
18 Text6 E M E R G E N C Y P O W E R S Y S T E M A S S E S S M E N T D A T A Item ID Description Emergency power system includes one emergency panelboard with feeder connected to emergency system located in Natural History Building. Overall Condition Fair Date Installed 1/1/1993 Remaining Useful Life 5 Years Nominal Useful Life: 25 Years Equipment Tag E-3 Manufacturer Westinghouse Model Number - Serial Number - Size/Capacity 100 A HP/kW - Voltage 120/208 V Material - Recommendation - Replacement Cost $35, PAGE 18
19 Text6 E M E R G E N C Y P O W E R S Y S T E M S U R V E Y P H O T O G R A P H S Emergency panelboard PAGE 19
20 Text6 I N T E R I O R L I G H T I N G - G R E E N H O U S E A S S E S S M E N T D A T A Item ID Description Illumination in greenhouse includes metal halide fixtures with illumination levels required for plants grow research. Overall Condition Poor Date Installed 1/1/1993 Remaining Useful Life 5 Years Nominal Useful Life: 25 Years Equipment Tag - Manufacturer - Model Number - Serial Number - Size/Capacity - HP/kW - Voltage 120 V Material - Recommendation -. Replacement Cost $56,000 Comments Wiring within greenhouse is deteriorating due to constant moisture and age PAGE 20
21 Text6 I N T E R I O R L I G H T I N G - G R E E N H O U S E S U R V E Y P H O T O G R A P H S Greenhouse corridor lighting Wiring in greenhouse Green house lighting PAGE 21
22 Text6 I N T E R I O R L I G H T I N G - H E A D H O U S E A S S E S S M E N T D A T A Item ID Description Office and storages are illuminated with fluorescent fixtures with T-12 lamps. Overall Condition Poor Date Installed 1/1/1993 Remaining Useful Life 5 Years Nominal Useful Life: 25 Years Equipment Tag - Manufacturer - Model Number - Serial Number - Size/Capacity - HP/kW - Voltage 120 V Material - Recommendation Replacement of light fixtures with new more efficient fixtures. Replacement Cost $13, PAGE 22
23 Text6 I N T E R I O R L I G H T I N G - H E A D H O U S E S U R V E Y P H O T O G R A P H S Head house lighting PAGE 23
24 Text6 E M E R G E N C Y L I G H T I N G S Y S T E M A S S E S S M E N T D A T A Item ID Description Emergency lighting includes selected light fixtures connected to emergency panelboard. Overall Condition Poor Date Installed 1/1/1993 Remaining Useful Life 5 Years Nominal Useful Life: 25 Years Equipment Tag - Manufacturer - Model Number - Serial Number - Size/Capacity - HP/kW - Voltage - Material - Recommendation - Replacement Cost $3, PAGE 24
25 PAGE 25
26 Text6 E X I T L I G H T I N G S Y S T E M A S S E S S M E N T D A T A Item ID Description Box type exit signs with 2 lamps Overall Condition Poor Date Installed 1/1/1993 Remaining Useful Life 5 Years Nominal Useful Life: 25 Years Equipment Tag - Manufacturer - Model Number - Serial Number - Size/Capacity - HP/kW - Voltage 120 V Material - Recommendation Replacement with LED type signs with battery back-up Replacement Cost $5, PAGE 26
27 Text6 E X I T L I G H T I N G S Y S T E M S U R V E Y P H O T O G R A P H S Typical exit sign at head house doors Exit sign PAGE 27
28 Text6 L I G H T I N G C O N T R O L S Y S T E M A S S E S S M E N T D A T A Item ID Description Partial Illumination in greenhouse is controlled by time clock switches. Overall Condition Poor Date Installed 1/1/1993 Remaining Useful Life Exceeded Nominal Useful Life: 20 Years Equipment Tag - Manufacturer - Model Number - Serial Number - Size/Capacity - HP/kW - Voltage 120 V Material - Recommendation Utilization of water proof electrical equipment in wet areas. Replacement Cost $22,700 Comments Wiring within greenhouse is deteriorating due to moisture and age. Critical Issues Replacement of deteriorated time switches. Critical Repair Estimate $1, PAGE 28
29 Text6 L I G H T I N G C O N T R O L S Y S T E M S U R V E Y P H O T O G R A P H S Wiring in greenhouse Timers in greenhouse Timers for lighting PAGE 29
30 Text6 E X T E R I O R L I G H T I N G A S S E S S M E N T D A T A Item ID Description Incandescent fixtures at Greenhouse and one wall mounted metal halide light fixtures provide exterior illumination. Overall Condition Poor Date Installed 1/1/1993 Remaining Useful Life 5 Years Nominal Useful Life: 25 Years Equipment Tag - Manufacturer - Model Number - Serial Number - Size/Capacity - HP/kW - Voltage 120V Material - Recommendation Replacement of all fixtures and add walkway lighting Replacement Cost $13, PAGE 30
31 Text6 E X T E R I O R L I G H T I N G S U R V E Y P H O T O G R A P H S Open lamp fixtures above greenhouse entry Ornamental fixtures at East side West side-no lights PAGE 31
32 Text106 C O M M U N I C A T I O N S D I S C I P L I N E R E P L A C E M E N T C O S T S U M M A R Y DATA SYSTEM SYSTEM/COMPONENT Communication Infrastructure System COMMUNICATIONS TOTAL % OF TOTAL POOR (1-5 YEARS) E X P E C T E D R E M A I N I N G S E R V I C E L I F E FAIR GOOD (5-10 YEARS) (10-20 YEARS) EXCELLENT (20+ YEARS) TOTAL 38,300 38,300 38,300 38, PAGE 32
33 Text6 C O M M U N I C A T I O N I N F R A S T R U C T U R E S Y S T E M A S S E S S M E N T D A T A Item ID Description The building is fed with 12 strands of single mode fiber and 25 copper pairs with each pair grounded and individually protected by a fuse/surge arrestor. Fiber and copper originate from Node #2. The building IDF is located in room 6 at the Basement level. Fiber distributes radially from the building IDF to a single hub cabinet adjacent to the IDF in the same room and lands at the cabinet mounted fiber switch within the hub cabinet. The room that the hub is located in is monitored by a smoke detector. There is no dedicated room HVAC The building is typically equipped with WIFI throughout (coverage not noted). Overall Condition Good Date Installed UIUC network upgrade complete (date range 2006 to 2012) Remaining Useful Life 20 Years Nominal Useful Life: 20 Years Replacement Cost $38,300 Comments IDF are is poorly lit and located in the steam tunnel that is damp and hot PAGE 33
34 Text6 L E G A C Y A S S E T D E S C R I P T I O N : N A T U R A L H I S T O R Y S U R V E Y G R E E N H O U S E The Natural History Survey Greenhouse contains one floor and a basement. The building consists of mechanical and electrical rooms, building service storage, a research laboratory, administrative offices, and a greenhouse. The Life Safety Code classifies the building as Mixed Occupancy (part Business, part Storage). The Natural History Survey Greenhouse has a manual and automatic fire alarm system. One manual pull station is located at the first floor exit from Room 101 to 111. Automatic fire detection is located in the lower floor (Room 001). Occupant notification is by an audible/visual alarm located in the first floor (Room 101). There exists no fire alarm control panel for the building. The Natural History Survey Greenhouse has no observable emergency lighting or emergency power systems. The Natural History Survey Greenhouse is a non-sprinklered building with a no standpipe system. There exists no fire department connection into the building. OCCUPANT LOAD/EXITING First Floor (LED): 85 occupants; 2 exits required (9 exits provided); 17" exit door width required (312" provided); door and corridor widths are sufficient for occupants served. Basement Floor: 15 occupants; two exits required (1 exit provided); the exit width including stairs/doors provides capacity for 173 occupants. Door and stair widths are sufficient for occupants served PAGE 34
35 N A T U R A L H I S T O R Y S U R V E Y G R E E N H O U S E L E G A C Y A S S E S S M E N T S U M M A R Y Item ID REQUIREMENT NUMBER INSPECTION DATE IDENTIFIED ISSUE LEGACY VALUE PERCENT COMPLETE POOR FAIR CODE TOTAL GENERAL LEGACY ITEMS ITEMS REQ /13/2005 Stairs: Refinish Wood Treads and Risers REQ /13/2005 Exterior Doors: Aged 53, ,600 53, REQ /13/2005 Greenhouse: Aged, Worn and Deteriorated 1,050, ,050,100 1,050, REQ /13/2005 Roof: Built-Up Tar and Gravel Cover Is Aged 18, ,900 18, REQ /13/2005 Exterior Walls: Cracked Foundation 8, ,000 8, REQ /13/2005 Exterior Wall: Missing or Loose Mortar 29, ,300 29, REQ /13/2005 Exterior Windows: Aged (Historical Type) 37, ,200 37, REQ /4/2005 Means of Egress: Number of Exits 27, ,700 27, REQ /4/2005 Means of Egress: Stair Enclosure 9, ,400 9, REQ /4/2005 Means of Egress Components: Door Swing GENERAL LEGACY ITEMS TOTALS 1,234, ,234,900 1,234,900 MEP LEGACY ITEMS ITEMS REQ /8/2002 Data: Upgrade Network Infrastructure 14, ,800 14,800 MEP LEGACY ITEMS TOTALS 14, ,800 14,800 TOTALS 1,249, ,234,900 14,800 1,249,700 % OF LEGACY VALUE Poor = VFA Priorities 1,2, and 3; Fair VFA Priority 4; and Code VFA Priority PAGE 35
36 Text6 L E G A C Y A S S E S S M E N T D A T A : R E Q Date Inspected 1/13/2005 Description Requirement Category Requirement Name Condition The finish on the wood stairs is worn. Appearance Stairs: Refinish Wood Treads and Risers (Legacy) Poor Percent Complete 0.0 Recommendation Refinish the wood stairs. Estimated Cost Estimated Remaining Cost: Action Date 1/13/2010 Text6 L E G A C Y A S S E S S M E N T D A T A : R E Q Date Inspected 1/13/2005 Description Requirement Category Requirement Name Condition The exterior door show signs of wear and tear. These units have exceeded their design life expectancy. Beyond Useful Life Exterior Doors: Aged (Legacy) Poor Percent Complete 0.0 Recommendation Replace exterior doors throughout the facility. Estimated Cost 53, Estimated Remaining Cost: 53, Action Date 1/13/ PAGE 36
37 Text6 L E G A C Y A S S E S S M E N T D A T A : R E Q Date Inspected 1/13/2005 Description Requirement Category Requirement Name Condition The greenhouse portion of this facility consists of single pane glazed wood sash (roof and walls) on steel frame. The sash is in poor condition and the cost to recondition would be substantially more than the cost to replace the greenhouse. Building Code Greenhouse: Aged, Worn and Deteriorated (Legacy) Poor Percent Complete 0.0 Recommendation Replace greenhouse shell. (Approximately 37' x 100') Estimated Cost 1,050, Estimated Remaining Cost: 1,050, Action Date 1/13/2010 Text6 L E G A C Y A S S E S S M E N T D A T A : R E Q Date Inspected 1/13/2005 Description Requirement Category Requirement Name Condition The existing built-up roof over room 101 is actively leaking and beyond its expected useful lifecycle. Integrity Roof: Built-Up Tar and Gravel Cover Is Aged (Legacy) Poor Percent Complete 0.0 Recommendation Replace entire existing built-up roof with an EPDM roofing system. Estimated Cost 18, Estimated Remaining Cost: 18, Action Date 1/13/ PAGE 37
38 Text6 L E G A C Y A S S E S S M E N T D A T A : R E Q Date Inspected 1/13/2005 Description Requirement Category Requirement Name Condition The foundation wall is structurally unsound. The remaining exterior foundation needs repointing. Integrity Exterior Walls: Cracked Foundation (Legacy) Poor Percent Complete 0.0 Recommendation The cracks and spalled concrete need to be cleaned of loose material and filled to prevent further deterioration. Estimated Cost 7, Estimated Remaining Cost: 7, Action Date 1/13/2008 Text6 L E G A C Y A S S E S S M E N T D A T A : R E Q Date Inspected 1/13/2005 Description Requirement Category Requirement Name Condition The mortar joints in the exterior masonry walls have aged to a point where they appear porous and ineffective in repelling moisture. Integrity Exterior Wall: Missing or Loose Mortar (Legacy) Poor Percent Complete 0.0 Recommendation Provide tuck pointing at indicated locations. Estimated Cost 29, Estimated Remaining Cost: 29, Action Date 1/13/ PAGE 38
39 Text6 L E G A C Y A S S E S S M E N T D A T A : R E Q Date Inspected 1/13/2005 Description Requirement Category Requirement Name Condition The building's fenestration consists of double hung wood sash in wood frames with single pane glazing. They are in poor to fair condition due to age, deteriorated sealant and glazing compound, water infiltration and peeling paint. Due to the age and prominence of the building, the windows should be replaced with a historical profile, double-glazed, thermally sealed wood window with aluminum cladding. Integrity Exterior Windows: Aged (Historical Type) (Legacy) Poor Percent Complete 0.0 Recommendation Remove the existing antiquated windows and replace with a historical profile, double glazed, thermally sealed wood window with aluminum cladding. The costs listed below are for budgetary consideration only. The selection of type, material and construction of historical windows are outside of the scope of VFA services. Estimated Cost 37, Estimated Remaining Cost: 37, Action Date 1/13/2010 Text6 L E G A C Y A S S E S S M E N T D A T A : R E Q Date Inspected 11/4/2005 Description There exists one exit from the basement Business Occupancy. This is not compliant with NFPA 101 Section Requirement Category Requirement Name Condition Life Safety Means of Egress: Number of Exits (Legacy) Poor Percent Complete 0.0 Recommendation Install an outside stair from Room 003 on the north exterior wall with exit discharge at grade. Estimate includes construction of new stair from basement to grade. Adjustment factor of 1.6 used to account for additional costs typically associated with retrofit work, working with existing construction, and significant unknowns/variables due to complexity. Estimated Cost 27, Estimated Remaining Cost: 27, Action Date 11/4/ PAGE 39
40 Text6 L E G A C Y A S S E S S M E N T D A T A : R E Q Date Inspected 11/4/2005 Description Stair 1 is a required exit and is an unenclosed stair. This is not compliant with NFPA 101 Section Requirement Category Requirement Name Condition Life Safety Means of Egress: Stair Enclosure (Legacy) Poor Percent Complete 0.0 Recommendation Stair 1: First Floor (Per Exception to ) - Install one new 1-hour fire rated door assembly from 101 to 103 and 101 to 111. Install electronic hold-open devices to tie-in to recommended fire alarm system. Adjustment factor of 1.6 used to account for additional costs typically associated with retrofit work, working with existing construction, and significant unknowns/variables due to complexity. Estimated Cost 9, Estimated Remaining Cost: 9, Action Date 11/4/2006 Text6 L E G A C Y A S S E S S M E N T D A T A : R E Q Date Inspected 11/4/2005 Description There exist two exit discharge doors, located in the first floor Room 111, that do not swing in the direction of egress travel. This is not compliant with NFPA 101 Section nor the exceptions of Requirement Category Requirement Name Condition Life Safety Means of Egress Components: Door Swing (Legacy) Poor Percent Complete 0.0 Recommendation Reinstall the exit doors to swing in the direction of egress travel. Estimated Cost Estimated Remaining Cost: Action Date 11/4/ PAGE 40
41 Text6 L E G A C Y A S S E S S M E N T D A T A : R E Q Date Inspected 10/8/2002 Description Requirement Category Requirement Name Condition Upgrade existing voice/data system to Cat 5 or Cat 6 to meet occupant requirements. Voice/Data System Data: Upgrade Network Infrastructure (Legacy) Fair Percent Complete 0.0 Recommendation (Cont. from Deficiency) The dollar estimates are based on a combination of average costs drawn from completed building upgrade projects, the existence of partial network upgrades, and physical challenges a building may pose. The estimates DO NOT include costs for constructing Communication Equipment Rooms, additional power, or additional cooling needed for network equipment. CITES has typically never borne these costs and has no tracking history for them. There may be a several week delay between the completion of a project and the updating of CITES wiring/jack database; thus, the number of jacks most recently added may not be reflected in this list. Only campus buildings for which CITES has a record of data jacks are included on this list. Housing buildings and campus-leased buildings are not included on this list. Estimated Cost 14, Estimated Remaining Cost: 14, PAGE 41
ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 2/6/2013 BUILDING SURVEY DATE
0133 608 EAST PENNSYLVANIA AVENUE CHAMPAIGN, ILLINOIS 61820 SYSTEM CONDITION INDEX.516 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 646,900 PARKING STRUCTURE BUILDING GROSS
More informationORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 2/15/2013 BUILDING SURVEY DATE
0807 3502 SOUTH FIRST STREET CHAMPAIGN, ILLINOIS SYSTEM CONDITION INDEX.771 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 347,400 LABORATORY BUILDING GROSS SQUARE FEET 16,986
More informationORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 6/19/2013 BUILDING SURVEY DATE
0154 52 EAST GREGORY DRIVE CHAMPAIGN, ILLINOIS 61820 SYSTEM CONDITION INDEX.646 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 1,203,500 OFFICE BUILDING GROSS SQUARE FEET
More informationORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 4/11/2013 BUILDING SURVEY DATE
0040 1402 WEST PENNSYLVANIA AVENUE URBANA, ILLINOIS 61801 SYSTEM CONDITION INDEX.685 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 1,364,800 LECTURE HALL BUILDING GROSS SQUARE
More informationORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 6/6/2013 BUILDING SURVEY DATE
0222 54 EAST GREGORY DRIVE CHAMPAIGN, ILLINOIS 61820 SYSTEM CONDITION INDEX.722 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 3,473,300 DISTRIBUTION BUILDING GROSS SQUARE
More informationORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 6/6/2013 BUILDING SURVEY DATE
0002 1301 SOUTH GOODWIN AVENUE URBANA, ILLINOIS 61801 SYSTEM CONDITION INDEX.862 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 746,400 CLASSROOMS / LIBRARY BUILDING GROSS
More informationORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 6/6/2013 BUILDING SURVEY DATE
0004 1103 SOUTH SIXTH STREET CHAMPAIGN, ILLINOIS 61820 SYSTEM CONDITION INDEX.810 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 1,831,000 CLASSROOMS / LIBRARY BUILDING GROSS
More informationORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 6/5/2013 BUILDING SURVEY DATE
0062 1105 WEST NEVADA STREET URBANA, ILLINOIS 61801 SYSTEM CONDITION INDEX.850 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 2,286,000 LABORATORY BUILDING GROSS SQUARE FEET
More informationORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 6/4/2013 BUILDING SURVEY DATE
0218 504 EAST ARMORY AVENUE CHAMPAIGN, ILLINOIS 61820 SYSTEM CONDITION INDEX.764 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 1,714,300 OFFICE BUILDING GROSS SQUARE FEET
More informationORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 6/18/2013 BUILDING SURVEY DATE
0358 1004 SOUTH FOURTH STREET CHAMPAIGN, ILLINOIS 61820 SYSTEM CONDITION INDEX.508 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 2,281,700 CLASSROOMS / LIBRARY BUILDING GROSS
More informationORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 6/18/2013 BUILDING SURVEY DATE
0238 URBANA, ILLINOIS 61801 SYSTEM CONDITION INDEX.183 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 1,237,600 OFFICE BUILDING GROSS SQUARE FEET 18,054 NUMBER OF BUILDING
More informationORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 4/19/2013 BUILDING SURVEY DATE
0220 500 EAST PEABODY DRIVE CHAMPIAGN, ILLINOIS 61820 SYSTEM CONDITION INDEX.364 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 4,262,400 MUSEUM BUILDING GROSS SQUARE FEET
More informationORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 6/3/2013 BUILDING SURVEY DATE
0006 505 EAST AVENUE CHAMPAIGN, ILLINOIS 61820 SYSTEM CONDITION INDEX.492 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 10,114,300 BUILDING GROSS SQUARE FEET 260,748 NUMBER
More informationORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 02/08/2013 BUILDING SURVEY DATE
0171 1503 SOUTH MARYLAND DRIVE URBANA, ILLINOIS 61801 SYSTEM CONDITION INDEX.770 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 2,686,100 LABORATORY BUILDING GROSS SQUARE
More informationORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 4/17/2013 BUILDING SURVEY DATE
0039 1114 WEST NEVADA STREET URBANA, ILLINOIS 61801 SYSTEM CONDITION INDEX.766 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 9,578,600 CLASSROOMS / LIBRARY BUILDING GROSS
More informationORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 2/13/2013 BUILDING SURVEY DATE
0197 1102 SOUTH GOODWIN AVENUE URBANA, ILLINOIS 61801 SYSTEM CONDITION INDEX.644 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 11,554,400 LABORATORY BUILDING GROSS SQUARE
More informationORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 4/10/2013 BUILDING SURVEY DATE
0110 23 EAST STADIUM DRIVE CHAMPAIGN, ILLINOIS 61820 SYSTEM CONDITION INDEX.838 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 3,161,900 LABORATORY BUILDING GROSS SQUARE FEET
More informationORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 2/4/2013 BUILDING SURVEY DATE
0156 504 EAST PENNSYLVANIA AVENUE CHAMPAIGN, ILLINOIS 61820 SYSTEM CONDITION INDEX.461 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 16,618,500 CLASSROOMS / LIBRARY BUILDING
More informationListing of Events Fort McMurray Roman Catholic Seperate School District Fr. M. Beauregard School
Fort McMurray Roman Catholic Seperate School District Fr. M. Beauregard School Building Events 2004 2005 2006 2007 2008 Total Code Repair Add ventilation to storage room $ 1,000.00 $ - $ - $ - $ - $ 1,000.00
More informationAnson County Early College High
NC School District/040 Anson County/High School Anson County Early College High Final Campus Assessment Report March 11, 2017 PARSONS Campus Assessment Report Table of Contents Campus Executive Summary
More informationPleasantdale Elementary
DeKalb County School District/Elementary Schools Pleasantdale Elementary Final School Assessment Report May 20, 2016 PARSONS School Assessment Report Table of Contents School Executive Summary 5 School
More informationSubject: Capital Reserve Expenditure Guidelines. *incl. former OCHAP/CSHP Peel Access to Housing (PATH)
HIP Housing In Peel Subject: Capital Reserve Expenditure Guidelines Date: August 1, 2012 Applicable To The information contained in this document applies to the following: Municipal & Private Non- Federal
More informationNC School District/430 Harnett County/Middle School Highland Middle Final Campus Assessment Report March 11, 2017
NC School District/430 Harnett County/Middle School Highland Middle Final Campus Assessment Report March 11, 2017 PARSONS Campus Assessment Report Table of Contents Campus Executive Summary 5 Campus Dashboard
More informationHarnett Central High
NC School District/430 Harnett County/High School Harnett Central High Final Campus Assessment Report March 11, 2017 PARSONS Campus Assessment Report Table of Contents Campus Executive Summary 6 Campus
More informationPinebrook Elementary
NC School District/300 Davie County/Elementary School Pinebrook Elementary Final Campus Assessment Report March 10, 2017 PARSONS Campus Assessment Report Table of Contents Campus Executive Summary 6 Campus
More informationBob Mathis Elementary
DeKalb County School District/Elementary Schools Bob Mathis Elementary Final School Assessment Report May 19, 2016 PARSONS School Assessment Report Table of Contents School Executive Summary 4 School Condition
More informationHowsyth Court Condominium Corporation No. CCN Avenue SW Calgary, Alberta
Entuitive Corporation Calgary + Toronto Howsyth Court Condominium Corporation No. CCN9011190 305 25 Avenue SW Calgary, Alberta Submitted By: Entuitive Corporation 209 8 th Avenue SW, Suite 300 Calgary,
More informationSagamore Hills Elementary
DeKalb County School District/Elementary Schools Sagamore Hills Elementary Final School Assessment Report May 20, 2016 PARSONS School Assessment Report Table of Contents School Executive Summary 4 School
More informationDavie County Early College High
NC School District/300 Davie County/High School Davie County Early College High Final Campus Assessment Report March 10, 2017 PARSONS Campus Assessment Report Table of Contents Campus Executive Summary
More informationLaurel Hill Elementary
NC School District/830 Scotland County/Elementary School Laurel Hill Elementary Final Campus Assessment Report March 11, 2017 PARSONS Campus Assessment Report Table of Contents Campus Executive Summary
More informationNC School District/520 Jones County/Elementary School Trenton Elementary Final Campus Assessment Report March 11, 2017
NC School District/520 Jones County/Elementary School Trenton Elementary Final Campus Assessment Report March 11, 2017 PARSONS Campus Assessment Report Table of Contents Campus Executive Summary 4 Campus
More informationSocial Housing Administration Directive No
Regional Municipality of Halton Social Housing Administration Directive No. 06-05 Date: August 30, 06 To: Federally-Funded Social Housing Providers subject to Operating Agreements under Section 95 of the
More informationMountain Heritage High
NC School District/995 Yancey County/High School Mountain Heritage High Final Campus Assessment Report March 12, 2017 PARSONS Campus Assessment Report Table of Contents Campus Executive Summary 7 Campus
More informationBacklog Reduction Plan
2003-2013 Executive Summary proposes to achieve reductions in our facilities maintenance backlog by documenting and completing backlog projects on a priority basis and by minimizing or eliminating future
More informationUrban Heights Condominium
Condominium Capital 2011 2010, AssociationAnalysis, LLC Condominium Prepared For: Table of Contents Condominium Association, Inc. 1642 Maxwell Road Atlanta, GA 30012 October 19, 2010 INTRODUCTION INTRODUCTION
More informationDeKalb Elementary School of the Arts at Terry Mills
DeKalb County School District/Elementary Schools DeKalb Elementary School of the Arts at Terry Mills Final School Assessment Report May 19, 2016 PARSONS School Assessment Report Table of Contents School
More informationRobert Shaw Theme Elementary
DeKalb County School District/Elementary Schools Robert Shaw Theme Elementary Final School Assessment Report May 20, 2016 PARSONS School Assessment Report Table of Contents School Executive Summary 4 School
More informationNC School District/430 Harnett County/Elementary School Gentry Primary Final Campus Assessment Report March 11, 2017
NC School District/430 Harnett County/Elementary School Gentry Primary Final Campus Assessment Report March 11, 2017 PARSONS Campus Assessment Report Table of Contents Campus Executive Summary 6 Campus
More informationAnderson Creek Primary
NC School District/430 Harnett County/Elementary School Anderson Creek Primary Final Campus Assessment Report March 11, 2017 PARSONS Campus Assessment Report Table of Contents Campus Executive Summary
More informationTO MEMBERS OF THE COMMITTEE ON GROUNDS AND BUILDINGS: ACTION ITEM
104 Office of the President TO MEMBERS OF THE COMMITTEE ON : For Meeting of ACTION ITEM AMENDMENT OF THE BUDGET FOR CAPITAL IMPROVEMENTS AND THE CAPITAL IMPROVEMENT PROGRAM AND APPROVAL OF EXTERNAL FINANCING
More informationWhat did they tell me?
LBS Insurance Commission Oct 25, 2018 What did they tell me? Handouts from the October 25, 2018 Insurance Town Hall C R. Reynolds 1 High Level Recap of Changes for 2018-19 Deductible $5,000 -> $25,000
More informationHarnett Central Middle
NC School District/430 Harnett County/Middle School Harnett Central Middle Final Campus Assessment Report March 11, 2017 PARSONS Campus Assessment Report Table of Contents Campus Executive Summary 5 Campus
More informationLilesville Elementary
NC School District/040 Anson County/Elementary School Lilesville Elementary Final Campus Assessment Report March 11, 2017 PARSONS Campus Assessment Report Table of Contents Campus Executive Summary 4 Campus
More informationCentral Davie Academy
NC School District/300 Davie County/High School Central Davie Academy Final Campus Assessment Report March 10, 2017 PARSONS Campus Assessment Report Table of Contents Campus Executive Summary 4 Campus
More informationDeKalb County School District/Elementary Schools Dunwoody Elementary Final School Assessment Report May 19, 2016
DeKalb County School District/Elementary Schools Dunwoody Elementary Final School Assessment Report May 19, 2016 PARSONS School Assessment Report Table of Contents School Executive Summary 4 School Condition
More informationLafayette Elementary
NC School District/430 Harnett County/Elementary School Lafayette Elementary Final Campus Assessment Report March 11, 2017 PARSONS Campus Assessment Report Table of Contents Campus Executive Summary 5
More informationCity School District of Albany Five Year Facilities Plan 3/14/2019
Bold indicates change from 3/7/19 BOE meeting Available Local Share $ 3,300,000 1 SPA Air condition gymnasium $ 267,000 1 $ 41,385 $ 41,385 $ 267,000 2 DCS Air condition gymnasium $ 221,000 1 $ 34,255
More informationReference: The Bel-Harbour Condominium Association Reserve Study Update Kipcon Great Lakes Project No CRU
August 18, 2016 Mr. Nicholas Burbulis 420 W. Belmont Ave. Chicago, IL 60657 Reference: The Kipcon Great Lakes Dear Mr. Burbulis: Attached, please find Kipcon Great Lakes, which has been prepared for the.
More informationStone Mountain Middle
DeKalb County School District/Middle Schools Stone Mountain Middle Final School Assessment Report May 20, 2016 PARSONS School Assessment Report Table of Contents School Executive Summary 4 School Condition
More informationDeKalb County School District/High Schools Druid Hills High Final School Assessment Report May 19, 2016
DeKalb County School District/High Schools Druid Hills High Final School Assessment Report May 19, 2016 PARSONS School Assessment Report Table of Contents School Executive Summary 5 School Condition Summary
More informationUpdate With Site Visit
Update With Site Visit Le Chateau Bellevue, WA 10/28/2011 Report #1002 Phone: 253-241-8151 Fax: 360-872-8073 E-mail: jeremy@reservesolutions.net www.reservesolutions.net Le Chateau Client Info: REPORT
More informationBuilding Division Fees 2018
Building Division Fees 2018 Permit Administration A permit administration fee of $45.00 shall be assessed for each permit. Staff Consultation Fee $75.00 Administration Determination $90.00 / hour; $23.00
More informationWilliam Bradley Bryant Center
DeKalb County School District/Education Other William Bradley Bryant Center Final School Assessment Report May 19, 2016 PARSONS School Assessment Report Table of Contents School Executive Summary 4 School
More informationReserve Analysis Report
Reserve Analysis Report Parkway Towers 1155 Ash St Denver, CO 80220 Level I Study with Site Inspection Fiscal Year End Date: 12/31/2014 8597 Via Mallorca Suite E La Jolla, CA 92037 Phone: 858-764-1895
More informationProtecting your older home
Protecting your older home HOMEOWNERS INSURANCE Helping you protect your biggest investment: your home At Travelers, we care about our homeowners. We want you to get the most out of the older home you
More informationREPLACEMENT RESERVE GUIDE
CANADA MORTGAGE AND HOUSING CORPORATION REPLACEMENT RESERVE GUIDE What is the Replacement Reserve? The replacement reserve is a fund kept by each housing sponsor under the terms of its operating agreement
More informationRonald E. McNair Discovery Learning Academy
DeKalb County School District/Elementary Schools Ronald E. McNair Discovery Learning Academy Final School Assessment Report May 20, 2016 PARSONS School Assessment Report Table of Contents School Executive
More informationGARDEN HOMES AT CHARBONNEAU GREEN TOWNHOME ASSOCIATION MAINTENANCE PLAN LEVEL I: FULL RESERVE STUDY FUNDING ANALYSIS 2012
GARDEN HOMES AT CHARBONNEAU GREEN TOWNHOME ASSOCIATION MAINTENANCE PLAN LEVEL I: FULL RESERVE STUDY FUNDING ANALYSIS 2012 www.schwindtco.com (503)227-1165 Page 1 of 49 GARDEN HOMES AT CHARBONNEAU GREEN
More informationProperty Assessment Form Property Data. Servicer and Loan Data
Property Data Property Name: Holmead Apartments Property Address: 3435 Holmead Place NW Change from previously reported City: Washington State: DC Zip: 20010 # Units: 101 # Buildings: 1 Year Built: 1951
More informationCondominium. Travelers Condominium Pac SM and Condominium Pac Plus SM are designed for owners of buildings used exclusively as condominiums.
25 Condominium Travelers Condominium Pac SM and Condominium Pac Plus SM are designed for owners of buildings used exclusively as condominiums. Eligibility Up to $10 million Total Insured Values per building,
More informationWashingtonville Central School District Building Condition Survey Five Year Plan
Building Condition Survey Five Year Plan Project Cost Summary Building 2011 2012 2013 2014 2015 Totals 0001 Washingtonville Jr High School $38,759 $325,990 $1,882,653 $1,417,341 $1,025,559 $4,690,302 0002
More informationFalls & Floods. Protecting your Office
Falls & Floods Protecting your Office Presented by: Brokers Trust Insurance Group Inc. Steve Campanella, Broker of Record Doriana Di-Fiore Isaguirre, Program Co-Ordinator Date: January 13 th, 2016 FLOOD,
More informationWarranty Information
Warranty Information Home warranty extension Page 2 SMART Home Protection Plan Page 2 90 Day Warranty Page 3 SewerGard Warranty Page 5 MoldSafe Warranty Page 7 Radon Warranty Page 9 5 Year Platinum Roof
More informationEducational & Performing Arts Center: Downriver Campus
Educational & Performing Arts Center: Total Estimated Project Construction Cost: $ 18.04 million Groundbreaking: September 2006 Percentage Completed: 100 percent Anticipated Completion Date: Completed
More informationOur Focus: Your Future
Town of Fort Erie Infrastructure Services Our Focus: Your Future Prepared for Council-in-Committee Report No. IS-53-07 Agenda Date November 19, 2007 File No. 220102 Subject 5 YEAR FACILITY CONDITION STATUS
More informationBUILDING PERMIT FEES
BUILDING PERMIT FEES 1. Building Permit Fee Based on the Construction Valuation of the project excluding site work. Refer to Fee Charts below. Electrical, Mechanical and Plumbing permits are not included
More informationFacility Condition Assessment. Facility Condition Assessment 8/13/2013 AGENDA
AGENDA benefits & limitations Rod Moore, RA, LEED AP, PMP Georgia Tech Benjamin Dutton, FFB, MCIOB, MRICS Faithful+Gould GT Facilities GT Program What is GT FCA Deliverables How GT uses FCA Information
More informationDEPRECIATION REPORT Strata VR 1591 The Leicester West 13th Avenue Vancouver BC V6J 2G5
DEPRECIATION REPORT 2015 Strata VR 1591 The Leicester 1545 West 13th Avenue Vancouver BC V6J 2G5 Created by Strata Council Members Merry Meredith Tom Heise Antoine Issa The authors have compiled this report
More informationWilliam Ellis Middle
NC School District/300 Davie County/Middle School William Ellis Middle Final Campus Assessment Report March 10, 2017 PARSONS Campus Assessment Report Table of Contents Campus Executive Summary 5 Campus
More informationTABLE OF CONTENTS - ADDENDUM NO. 3
TABLE OF CONTENTS - ADDENDUM NO. 3 TABLE OF CONTENTS Addendum No. 3 SUPPLEMENTAL INSTRUCTIONS TO BIDDERS SIB-1 SIB-2 SIB-3 Article I-2.4 - Contract Completion Time Article I-14.4 - Participation by SBE
More informationMocksville Elementary
NC School District/300 Davie County/Elementary School Mocksville Elementary Final Campus Assessment Report March 10, 2017 PARSONS Campus Assessment Report Table of Contents Campus Executive Summary 5 Campus
More informationIntegrating Green Building Measures into Capital Planning for HUD Assisted and Public Housing Programs
Building Bridges to Net Zero Integrating Green Building Measures into Capital Planning for HUD Assisted and Public Housing Programs Evolution of HUD's Green Capital Needs Assessment, and the new CNA etool
More informationRULES OF TENNESSEE DEPARTMENT OF COMMERCE AND INSURANCE DIVISION OF FIRE PREVENTION CHAPTER NEW MANUFACTURED HOMES AND RECREATIONAL VEHICLES
RULES OF TENNESSEE DEPARTMENT OF COMMERCE AND INSURANCE DIVISION OF FIRE PREVENTION CHAPTER 0780-2-4 NEW MANUFACTURED HOMES AND RECREATIONAL VEHICLES TABLE OF CONTENTS 0780-2-4-.01 Definitions 0780-2-4-.08
More informationReserve Fund Study My Condominium Plan
Reserve Fund Study My Condominium Plan 12 3456 Number of Units 36 Number of Buildings 1 Building Construction 21 Contact Ima Happy Position(s) President Contact Phone 43.555.4321 Report Date August 8,
More informationNUNAVUT HOUSING CORPORATION. Home Renovation Program (HRP)
NUNAVUT HOUSING CORPORATION Home Renovation (HRP) October 2014 Date October 201 TABLE OF CONTENTS OBJECTIVE... 1 SUMMARY... 1 ENABLING LEGISLATION... 1 ELIGIBLE CLIENTS... 1 PRIORITY OF APPLICANTS...
More informationMartin Luther King Jr. High
DeKalb County School District/High Schools Martin Luther King Jr. High Final School Assessment Report May 19, 2016 PARSONS School Assessment Report Table of Contents School Executive Summary 4 School Condition
More informationHome Buyer Pre Lending Package
Home Buyer Pre Lending Package Congratulations on the decision to buy a new home! The most important step in the home buying process is first obtaining a Mortgage Pre-Approval, and to understand the home
More informationTHE CLARIDGE OF POMPANO CONDOMINIUM, INC. ARCHITECTURAL REVIEW COMMITTEE REQUEST FOR MODIFICATION PART A - COMPLETED BY OWNER
THE CLARIDGE OF POMPANO CONDOMINIUM, INC. ARCHITECTURAL REVIEW COMMITTEE REQUEST FOR MODIFICATION PART A - COMPLETED BY OWNER I, of UNIT # request approval by the Architectural Review Committee for the
More informationPella Entry Door System Limited Lifetime Warranty
Pella Entry Door System Limited Lifetime Warranty Congratulations on choosing a Pella Entry Door System to protect and beautify your home. These superior-quality entry door systems have been designed to
More informationBUILDING CONDITION ASSESSMENT. A Comprehensive Approach in Energy and Facility Management
BUILDING CONDITION ASSESSMENT A Comprehensive Approach in Energy and Facility Management Presentation Outline Page Nadine International Company Profile.. 3 FCI -Industry Preferred Formula.... 4 FCI -Other
More informationCondominium Reserve Fund Planners Inc.
Condominium Reserve Fund Planners Inc. Reserve Fund Study York County Condominium Corporation No. 10 185 Reynolds Street Fredericton, NB E3A 0K7 Prepared for Board of Directors May 29, 2014 Table of Contents
More informationCITY OF EL SEGUNDO SCHEDULE B-1 BUILDING & SAFETY FEE SCHEDULE BUILDING PERMIT FEES PROPOSED
CITY OF EL SEGUNDO SCHEDULE B-1 BUILDING PERMIT FEES SERVICE PROPOSED FEE RESIDENTIAL BUILDING PERMITS Building Permit Under $500 Valuation $18.00 Building Permit $501-$2,000 Valuation $18 + $2.40 for
More informationRepairs responsibilities
Repairs responsibilities Repairs responsibilities for repairing and maintaining your home? This leaflet explains the basics about who is for repairs and maintenance within your home. For more detailed
More informationNC School District/430 Harnett County/Elementary School Coats Elementary Final Campus Assessment Report March 11, 2017
NC School District/430 Harnett County/Elementary School Coats Elementary Final Campus Assessment Report March 11, 2017 PARSONS Campus Assessment Report Table of Contents Campus Executive Summary 5 Campus
More informationLesson 2: The Homeowners Policy
Lesson 2: The Homeowners Policy Homeowners Insurance: ISO Policy Forms Covered Property to Identify and Address Residential Property and Liability Loss Exposures Four Methods for Managing Personal Residential
More informationReserve Fund Study prepared for The Greens at Pelican Point Homeowners Association February 2013 prepared by
Reserve Fund Study prepared for The Greens at Pelican Point Homeowners Association February 2013 prepared by Craig Naden and John Carlson Table of Contents TABLE OF CONTENTS Page No. 1.0 EXECUTIVE SUMMARY...
More informationOVERSIGHT OF MEASURE C SPENDING THE CITIZENS OVERSIGHT COMMITTEE
MEASURE C SCHOOL SAFETY AND MODERNIZATION On November 3, 2009 the voters residing in the Mill Valley School District (MVSD) approved the Measure C Safety and Modernization Bond of 2009 (Measure C). Measure
More informationProperty Inspection Guidelines
Property Inspection Guidelines www.tridentinsurance.net Lines of Business: Property, General Liability, Worker s Compensation, Public Official Liability Risk Control Strategy/Key Issues: Provide a tool
More informationHayfield Community Schools Bond Referendum. Vote Monday, September 11, Our Schools Our Communities Our Future
Hayfield Community Schools 2017 Bond Referendum Vote Monday, September 11, 2017 Our Schools Our Communities Our Future 2017 Bond Referendum What s Already Been Done? Studies and Meetings and Meetings 2014-15
More informationBuilding Permit Fees
Permit Center 210 Lottie Street, Bellingham, WA 98225 Phone: (360) 778-8300 Fax: (360) 778-8301 TTY: (360) 778-8382 Email: permits@cob.org Web: www.cob.org/permits Building Permit Fees This handout includes
More informationSAFETY CODES COUNCIL ORDER. BEFORE THE BUILDING TECHNICAL COUNCIL On February 22, 2012
SAFETY CODES COUNCIL #1000, 10665 Jasper Avenue N.W., Edmonton, Alberta, Canada, T5J 389 Tel: 780-413-0099 I 1-888-413-0099 Fax: 780-424-5134 I 1-888-424-5134 www.safetycodes.ab.ca ORDER COUNCIL ORDER
More informationFOR APARTMENTS SEGMENT
UNDERWRITING GUIDELINES FOR APARTMENTS SEGMENT Local exceptions to these underwriting guidelines may apply. Please consult with your underwriter or sales executive for details and to discuss risks which
More informationNOTE: CONSEQUENTIAL AND INCINDENTAL DAMAGES ARE EXCLUDED.
LIMITED WARRANTY TERM. The terms of the various coverages of this Limited Warranty begin on the date on which your home is deeded or possession of the completed homes is otherwise transferred to you. That
More informationPROFESSIONAL RESERVE STUDY
PROFESSIONAL RESERVE STUDY Seavue Condominiums 130-5 th Avenue South, Edmonds, WA 98020 For: Seavue Homeowners Association c/o Jay Grant Board President (202) 351-9399 Prepared By: Jeff Samdal, PE, RS,
More informationBody Corporate ten year maintenance plan example for South Africa
Body Corporate ten year maintenance plan example for South Africa Prepared by: Date: This plan covers the period of ten years from.. Building details & report inputs Supplied information Building name
More informationBest Practices Dealing With Vacant, Idle, Or Shut-Down Facilities
Global Asset Protection Services Best Practices Dealing With Vacant, Idle, Or Shut-Down Facilities By: Sobhy Girgis XL GAPS June 2011 Background Anticipating the Vacancies 85% to 90% of the time advance
More informationCITY OF TAMARAC BUILDING DEPARTMENT Schedule of Permit Fees
CITY OF TAMARAC BUILDING DEPARTMENT Schedule of Permit Fees SECTION I: As set forth in Section 105 of the Broward County Amendments to the 5th Edition (2014) Florida Building Code, it is unlawful for any
More informationWASHINGTON BROWN DEPRECIATION PTY LTD
Wednesday, 4 July 2007 The Owners - Strata Plan Number C/- Strata Management Company Address PROPERTY ADDRESS SINKING FUND FORECAST REPORT For the attention of: Strata Manager Dear Strata Manager, In accordance
More informationGreenbelt Homes, Inc Budget
Greenbelt Homes, Inc. 2015 Budget October 9, 2014 First Presentation Finance/Board of Directors November 6, 2014 First Reading November 20, 2014 Second Reading and Approval November 20, 2014 Second Reading
More informationFinal Report. Capital Plan Building Condition and Energy Assessments Khyber Building 1588 Barrington Street Halifax, Nova Scotia
Capital Management Engineering Limited EMPOWERING OUR CLIENTS WITH KNOWLEDGE 5531 Cornwallis Street, Halifax, NS, Canada B3K 1B3 Phone: 902 429 4412 Fax: 902 423 4945 Final Report Capital Plan Building
More information