McQuay BACnet Solution: Microtech II Applied Rooftop Unit Controller with Discharge Air Control (DAC)

Similar documents
Siemens Combustion Control Modbus Solution: LMV51

Square D Modbus Solution: Altivar 58 VFD

APOGEE Open Processor with Cummins/Onan Modbus Driver: PowerCommand System

LONWORKS Solution to Danfoss Graham VLT 6000 Adjustable Frequency Drive

Unit Ventilator Ceiling Water Source Heat Pump

June 15, City Of Rochelle 420 N 6th St Rochelle, IL Att: Ms. Sue Messer. UPDATED: Old Building / HVAC Controls and Energy Improvements

HVAC-4 Deemed Measures Uncertainty Study, Year 2

IEC : Annex F

Lightstream Scroll kW ULTRACOMPACT II FREECOOL COMPACT FREE COOLING CHILLERS WITH SCROLL COMPRESSORS

Lightstream Scroll kW ULTRACOMPACT II COMPACT AIR-COOLED CHILLERS WITH SCROLL COMPRESSORS

Limited Warranty Quality Pledge. Warranty effective for equipment manufactured after January 1, 2013.

PROGRAMMING GUIDE FOR PPC6000 SERIES

Draft Measure Information Template Cooling Tower Efficiency and Turndown

LPBC ALLOWANCES LPBC ADDENDUM # 4-11/13/17 SECTION

Limited Warranty Replacement Pledge. Warranty effective for equipment manufactured after January 1, 2013.

BUILDING PERMIT FEES

.! 4 5 2!, S E R V I C E P L A N S!)2

EXTENDED WARRANTY PROGRAM GUIDE. Qualifying Qualifying is easy. To participate, you must be registered with Factory Assurance Southwest ( FAS ).

AUSTIN. Request for Qualifications 19RFQ082 Testing and Balancing On Call Services. RFQ opening / due date at 2:00 pm CST

Residential Property Deduction Schedule

Be wattsmart and earn cash back.

Be wattsmart and earn cash back.

Prescriptive HVAC Application

EXTENDED WARRANTIES COMPREHENSIVE WARRANTY PROGRAM CUSTOMER PROTECTION PLAN

Building Optimization Analysis (BOA) Tool Training

Lightstream Scroll kW ULTRACOMPACT COMPACT AIR-COOLED CHILLERS WITH SCROLL COMPRESSORS

Texas Energy & Automation Management Solutions

HVAC Variable Frequency Drives Application. Application Process. Details & Instructions. Equipment Eligibility

ILLINOIS VALLEY COMMUNITY COLLEGE (Purchasing Department) 815 N. Orlando Smith Ave. Oglesby, Illinois REQUEST FOR PROPOSAL

LIMITED PARTS WARRANTY Air Conditioning, Heating and Ventilating Equipment Designed For Manufactured Housing

CITY OF EL SEGUNDO SCHEDULE B-1 BUILDING & SAFETY FEE SCHEDULE BUILDING PERMIT FEES PROPOSED

PRODUCT WARRANTY POLICIES AND PROCEDURES

Easystream kW PACKAGED SCROLL CHILLERS

Direct Install (DI) Program. Program Guide. Fiscal Year 2018 (7/1/2017 through 6/30/2018)

Yakima County Code ~ Building and Construction ~ Title FEES

Supersedes: 9/01/11 (Rev.5) Preparer: Owner: Approver: Team Member, North America Process Safety Center of Expertise

Tender document Estate Maintenance Department Web : Phone :

kW. Lightstream Screw V AIR-COOLED CHILLERS WITH SCREW COMPRESSORS

WHITE PLAINS MECHANICAL CODE PART 1. GENERAL REQUIREMENTS

HVAC Forensics: Uncovering the true cause of loss to HVAC systems. Curtis M. VanNess Field Operations Manager

Variable Frequency Drives Application - July 1, 2016 through June,

Rural Energy for America Program (REAP) Energy Efficiency & Conservation Loan Program (EECLP) and the Rural Energy Savings Program (RESP)

Functional Safety Safety Instrumented Systems in Process Industries August 2015

Optional Warranties. Dealer Program Guide

9124 Grand Avenue South Bloomington, MN (952) Toll Free (866)

The Best Products The Best Price The Best Service...We Guarantee It!

DESCRIPTION. High Sierra Systems ship complete with the following features and accessories:

HVAC Replacement Units

REQUEST FOR QUALIFICATIONS #2016-XXX

Direct Install (DI) Program. Program Guide. Fiscal Year 2019 (7/1/2018 through 6/30/2019)

Subcontractor Contract and Scope of Work MECHANICAL Social Security Administration Auburn, AL Ross Clark Circle Dothan, Alabama 36301

ADDENDUM #1 RFQ M1201M. 06/07/13 Please replace Chiller Maintenance Specifications with the attached Chiller Maintenance Specifications.

Warranty Policy & Procedures

Standard Motor Products, Inc. Annual Meeting of Shareholders May 18 th, 2017

Lightstream Scroll kW AIR-COOLED CHILLERS WITH SCROLL COMPRESSORS

HomeServe. HomeServe BUN1129 [XX]

Send application to address indicated below for customer s Electric Energy Efficiency Program Administrator. Electric Program Administrators

Functional Safety Demystified

Standard Motor Products, Inc. Q Investor Presentation

2018 Non-Residential Rebates

3M Super Close Projection System SCP712

2016 Residential HVAC Rebate Application

Parts List, Charging Chart, Wiring Diagrams

2018 Custom Energy Efficiency Incentives Program Procedures Manual

heating, ventilation and cooling systems incentive application for businesses

Contractor Service Agreement

PREMIUM PROTECTION PLAN HVAC PLUMBING GENERATOR

Home Comfort Certified System

Oregon Dry Cleaner Compliance Calendar

Warranty. This section outlines in detail the responsibilities of the Warranty Department: Administer warranty policies.

FLORIDA LIFE-CYCLE COST ANALYSIS PROGRAM For Sustainable State Agencies

R-407C REFRIGERANT LORC, LNH, LNL, LNQ AND LNX SERIES OUTDOOR AIR-COOLED REMOTE CONDENSERS STANDARD FEATURES VERTICAL DISCHARGE

2016 Statewide Retrocommissioning Policy & Procedures Manual

Energy Storage Systems (ESS): Preparing to Deal with the Hazards

Air Conditioner, Heat Pump, ECU, PTAC, GPac Warranty Statement and Policies

CAPITAL RESERVE FUNDING ANALYSIS

High Current Through Hole Inductor, High Temperature Series

TENDER DOCUMENT. for Supply, Installation & Commissioning of Equipment for Refrigeration And Air Conditioning (Training)

Powerstream Screw kW R134a WATER COOLED DUAL-CIRCUIT SCREW CHILLERS

IHLP-2525CZ-8A 22 μh ± 20 % ER e3 MODEL INDUCTANCE VALUE INDUCTANCE TOLERANCE PACKAGE CODE JEDEC LEAD (Pb)-FREE STANDARD MODEL SIZE PACKAGE CODE

IID APPLICATION INSTRUCTIONS ENERGY REWARDS PROGRAM FOR NON-RESIDENTIAL CUSTOMERS

BHARAT HEAVY ELECTRICALS LIMTIED 15TH FLOOR CENTRE - I, W.T.C. CUFFE PARADE, MUMBAI

2014 No ENERGY. The Domestic Renewable Heat Incentive Scheme Regulations 2014

Standard Motor Products, Inc. Q Investor Presentation

RRC STAFF OPINION PLEASE NOTE: THIS COMMUNICATION IS EITHER 1) ONLY THE RECOMMENDATION OF AN RRC

PROCEDURAL HISTORY AND FACTUAL BACKGROUND

Energy Efficiency Opportunities Report. AMP Limited Public Report

DAYTON METROPOLITAN HOUSING AUTHORITY dba GREATER DAYTON PREMIER MANAGEMENT

Spare parts DRYER. Antares. (50Hz) (Date )

ProSIS-FSE. SIL Calculator V1.6 User Guide

Tender Specification No.: 04 / of SE (CTI &Enqs.) / CTI, Dt: OPEN TENDER NOTICE

Questions by Vendors: District Answers are in Red. Vendor Questions are in Black.

Home Comfort Certified System

FEATURES. IHLP-2525CZ μh ± 20 % ER e3 MODEL INDUCTANCE VALUE INDUCTANCE TOLERANCE PACKAGE CODE JEDEC LEAD (Pb)-FREE STANDARD

OM Air Volume Booster Model : VF01. User's Manual

Customer Centricity Conference

BUILDING SUBCODE FEES:

Building Division Fees 2018

Trevor-Wilmot Consolidated School District Wilmot Road. Trevor, WI HVAC Preventative Maintenance. Request for Proposal

Snohomish PUD. Energy Services Team November 7, 2018

Transcription:

Point Map December 1, 2004 Systems Integration McQuay BACnet Solution: Microtech II Applied Rooftop Unit Controller with Discharge Air Control (DAC) Table 1. Microtech II Series 200 Applied Rooftop Unit Controller with Discharge Air Control Point Map, Application 4162. Point Type Range/Units abc 1 LAO Device Address 2 LAO Device Application 4162 3 LAI Unit Status See Table 2 4 LAI Cooling Capacity % 5 LAI Heating Capacity % 6 LAI Cooling Control Status See Table 3 7 LAO Heating Control Status See Table 4 8 LAO Application Mode SeeTable5 9 LDI VAV Box Output Off/On 10 LAI Occupancy 0=Occupied 1=Unoccupied 2=Bypass 11 LAO Occupancy Mode 0=Occupied 1=Unoccupied 2=Bypass 3=Auto 12 LAI Occupancy Source See Table 6 13 LDO Emergency Override Mode Flag No/Yes 14 LAI Control Temperature F 15 LAI Discharge Air Temperature F 16 LAI Return Air Temperature F 17 LAI Space Temperature F 18 LAI Outdoor Air Temperature F 19 LAI Entering Fan Temperature F continued on next page... Siemens Building Technologies, Inc. Page 1 of 10

Table 1. Microtech II Series 200 Applied Rooftop Unit Controller with Discharge Air Control Point Map, Application 4162. (continued) Point Type Range/Units abc 20 LDI Airflow Status No Flow/Flow 21 LDI Discharge Fan Status Off/On 22 LDI Return Fan Status Off/On 23 LDI Fan Operation Output Off/On 24 LAI Duct Static Pressure in WC Pa 25 LAO Duct Static Pressure Setpoint 0.2 to 4.0 in WC 49.8 to 995.4 Pa 26 LAI Discharge Fan Capacity % 27 LAI Building Static Pressure in WC Pa 28 LAO Building Static Pressure Setpoint 0.001 to 0.100 in WC 0.249 to 24.884 Pa 29 LAI Return Fan Capacity % 30 LAI Effective Cooling Enable Setpoint F 31 LAO Occupied Cooling Setpoint 0 to 99 F -17.8 to 37.3 32 LAO Control Temperature Source 0=Return 1=Space 2=Outside Air Temperature 33 LAO Unoccupied Cooling Setpoint 55 to 99 F 12.8 to 37.3 34 LAI Effective Heating Enable Setpoint F 35 LAO Occupied Heating Setpoint 0 to 99 F -17.8 to 37.3 36 LAO Unoccupied Heating Setpoint 0 to 99 F -17.8 to 37.3 37 LAI Effective Cooling Discharge Setpoint F 38 LAO Discharge Air Cooling Setpoint 40 to 100 F 4.5 to 37.8 39 LAO Minimum Discharge Air Cooling Setpoint 0 to 99 F -17.8 to 37.3 40 LAO Maximum Discharge Air Cooling Setpoint 0 to 99 F -17.8 to 37.3 41 LAI Outdoor Air Damper Position % 42 LAI Effective Minimum Outdoor Damper Position Setpoint % 43 LAI Outdoor Airflow cfm Lps continued on next page... Page 2 of 10 Siemens Building Technologies, Inc.

Table 1. Microtech II Series 200 Applied Rooftop Unit Controller with Discharge Air Control Point Map, Application 4162. (continued) Point Type Range/Units abc 44 LAO Outdoor Air Damper Minimum Position % 45 LAO Minimum Outdoor Airflow/Damper Position 0 to 50000 cfm 0to8.5x10 7 Lps 46 LDO Economizer Changeover Method Off = Enthalpy On = Dry Bulb Off/On 47 LAO Economizer Changeover Temperature Setpoint 0 to 99 F -17.8 to 37.3 48 LAI Effective Heating Discharge Setpoint F 49 LAO Discharge Air Heating Setpoint 40 to 100 F 4.5 to 37.8 51 LAO Minimum Discharge Air Heating Setpoint 0 to 99 F -17.8 to 37.3 52 LAO Maximum Discharge Air Heating Setpoint 0 to 99 F -17.8 to 37.3 53 LAI Energy Recovery Exhaust Temperature F 54 LAI Energy Recovery Supply Temperature F 61 LDO Occupancy Scheduler Input Unocc/Occ 62 LDO Remote Discharge Fan Capacity Control Flag Off = Duct Pressure On = Position Off/On 63 LAO Remote Discharge Fan Capacity Setpoint 0 to 100% 64 LAO Remote Return Fan Capacity Control Flag 0=None 1=Tracking 2=Building Pressure 3=Position 65 LAO Remote Return Fan Capacity Setpoint 0to100% 67 LDO Fault Status Clear Alarms or No Alarms Present/Alarms Present 68 LDO Problem Status Clear Alarms or No Alarms Present/Alarms Present 69 LDO Warning Status Clear Alarms or No Alarms Present/Alarms Present 70 LDI Fault - Alarm Output 71 LDI Fault - DAT Sensor Failure 72 LDI Fault - Discharge Vanes Stuck 73 LDI Fault - Excessive Discharge Compartment Pressure Sensed by DHL Sensor continued on next page... Siemens Building Technologies, Inc. Page 3 of 10

Table 1. Microtech II Series 200 Applied Rooftop Unit Controller with Discharge Air Control Point Map, Application 4162. (continued) Point Type Range/Units abc 74 LDI Fault - Airflow Not Sensed by PC7 After SAF Was Started 75 LDI Fault - Freezestat Condition While SAF On 76 LDI Fault - DAT Exceeded the Hi Disch Tmp Setting 77 LDI Fault - RAT Exceeded the Hi Return Tmp Setting 78 LDI Fault - DAT Fell Below the Lo Disch Tmp Setting 79 LDI Fault - OA Dampers < 50% Open After Startup (100% OA Units Only) 80 LDI Fault - OAT Sensor Failure While Selected as the Control Temperature Source 81 LDI Fault - RAT Sensor Failure 82 LDI Fault - Smoke Detected by SAF and/or RAF Smoke Detector 83 LDI Fault - Space Temp Sensor Failure When Control Temperature Source Parameter is Set to Space 84 LDI Problem-ClgEnableInputtoCCB1OffWhenCoolingWasOn 85 LDI Problem - Comm Failure Occurred Between MCB and CCB1 86 LDI Problem - Evaporator Coil Frost Condition Occurred on Ckt No. 1 87 LDI Problem - HP1 or HP3 Open Indicating Ckt No. 1 High Refrigerant Pressure 88 LDI Problem - LP1 Remained Opened After Ckt No. 1 Solenoid Valve Open 89 LDI Problem - LP1 Still Closed 180 Seconds into Ckt No. 1 Pumpdown Operation 90 LDI Problem-ClgEnableInputtoCCB2OffWhenCoolingWasOn 91 LDI Problem - Comm Failure Occurred Between MCBandCCB2 92 LDI Problem - Evaporator Coil Frost Condition Occurred on Ckt No. 2 93 LDI Problem - HP2 or HP4 Open Indicating Ckt No. 2 High Refrigerant Pressure 94 LDI Problem - LP2 Remained Opened After Ckt No. 2 Solenoid Valve Open 95 LDI Problem - LP2 Still Closed 180 Seconds into Ckt No. 2 Pumpdown Operation 96 LDI Problem - Comp No. 1 Off on Low Oil Pressure (OP1) or Motor Protector (MP1) 97 LDI Problem - Comp No. 2 Off on Low Oil Pressure (OP2) or Motor Protector (MP2) 98 LDI Problem - Comp No. 3 Off on Low Oil Pressure (OP3) or Motor Protector (MP3) 99 LDI Problem - Comp No. 4 Off on Low Oil Pressure (OP4) or Motor Protector (MP4) 100 LDI Problem-ClgEnableInputtoCCB1OffWhenCoolingWasOn continued on next page... Page 4 of 10 Siemens Building Technologies, Inc.

Table 1. Microtech II Series 200 Applied Rooftop Unit Controller with Discharge Air Control Point Map, Application 4162. (continued) Point Type Range/Units abc 101 LDI Problem - Comm Failure Occurred Between MCB and CCB1 102 LDI Problem - EFT Sensor Failure 103 LDI Problem - Airflow Not Sensed by PC7 After SAF Was Started 104 LDI Problem - Freezestat Tripped While SAF Was Off 105 LDI Problem - Comm Failure Occurred Between MCB and EHB1 107 LDI Problem - Htg Enable Input to EHB1 Off When Heating Was On 108 LDI Problem - Gas Furnace Safety Lockout Condition Occurred 109 LDI Problem - Excessive Temperature Rise Sensed Across Heat Section on Single Stage Heat Unit 110 LDI Problem - OAT Sensor Failure When Control Temperature Source Parameter Not Set to OAT 111 LDI Problem - RAT Sensor Failure Control Temperature Source Parameter Not Set to Return 112 LDI Problem - Space Temp Sensor Failure on Unit with RAT Sensor 113 LDI Warning-PC7SensedAirflow When Unit Was Off 114 LDI Warning-ClgenableInputtoCCB1OnWhenCoolingOff 115 LDI Warning - Clg Enable Input to CCB2 On When Cooling Off 116 LDI Warning - Condenser Board Hardware 117 LDI Warning - Pressure Drop Across First Filter Section Exceeded the Setting of PC5 118 LDI Warning - Pressure Drop Across Final Filter Section Exceeded the Setting of PC6 119 LDI Warning - Htg Enable Input to EHB1 On When HeatingOff 120 LDI Warning - OA Dampers Not at 0% When Unit Off or Not at 100% During Mechanical Cooling While Outdoor Ambient Parameter Indicates Low 121 LDI Problem - Comp No. 5 Off on Low Oil Pressure (OP5) or Motor Protector (MP5) 122 LDI Problem - Comp No. 6 Off on Low Oil Pressure (OP6) or Motor Protector (MP6) continued on next page... Siemens Building Technologies, Inc. Page 5 of 10

Table 1. Microtech II Series 200 Applied Rooftop Unit Controller with Discharge Air Control Point Map, Application 4162. (continued) Point Type Range/Units abc 127 LAI Current Fault See Table 7 128 LAI Current Problem See Table 8 129 LAI Current Warning See Table 9 a s noted for LDIs and LDOs are in the following format: OFF text/on text. b This column indicates the value/range or engineering units or both if known. c The default English value is not italicized. An italicized entry indicates an SI value. Unit Status (Point 03) Table 2. Unit Status s (Point 03). 0 Off-Unoccupied 1 Off-Network 2 Off-Switch 3 Off-Alarm 4 Calibration 5 Startup 6 Recirculation 7 Fan Only 8 Economizer 9 Cooling 10 Morning Warmup 11 Heating 12 Minimum Discharge Air Temperature 13 Unoccupied Economizer 14 Unoccupied Fan Only 15 Unoccupied Discharge Air Temperature 16 Unoccupied Cooling 17 Unoccupied Heating 18 Balance 19 Off-Manual 20 Manual Control Page 6 of 10 Siemens Building Technologies, Inc.

Cooling Control Status (Point 06) Table 3. Cooling Control Status s (Point 06). 0 All Cooling 1 Economizer 2 Mechanical Cooling 3 Off-Ambient 4 Off-Alarm 5 Off-None 6 Off-Balance 7 Off-Switch 8 Off-Network 9 Off-Manual Heating Control Status (Point 07) Table 4. Heating Control Status s (Point 07). 0 Heat Enabled 1 Off-Ambient 2 Off-Alarm 3 Off-None 4 Not Applicable 5 Off-Switch 6 Off-Network 7 Off-Manual Application Mode (Point 08) Table 5. Application Mode s (Point08). 0 Auto 1 Off 2 Heat Only 3 Cool Only 4 Fan Only Siemens Building Technologies, Inc. Page 7 of 10

Occupancy Source (Point 12) Table 6. Occupancy Source s (Point 12). 0 None 1 Initial Scheduler 2 Network Scheduler 3 Occupied Mode 4 Remote Switch 5 Not Applicable Current Fault (Point 127) Table 7. Current Fault s (Point 127). 0 No Active Faults 204 Outdoor Air Damper Stuck 208 Fan Failure 212 Low Discharge Air Temperature 216 High Discharge Air Temperature 220 High Return Air Temperature 224 Duct High Limit 228 Discharge Sensor Failure 232 Return Sensor Failure 236 Space Sensor Failure 240 Outdoor Air Sensor Failure 248 Smoke Fault 252 Freeze Fault Page 8 of 10 Siemens Building Technologies, Inc.

Current Problem (Point 128) Table 8. Current Problem s (Point 128). 0 NoActiveProblems 104 Energy Recovery Board Communication Failure 105 Heating Board Communication Failure 106 Generic Condenser Board Communication Failure 109 Compressor Board No. 2 Communication Failure 110 Compressor Board No. 1 Communication Failure 113 Heating Board Enable Failure 114 Generic Condenser Board Enable Failure 117 Compressor Board No. 2 Enable Failure 118 Compressor Board No. 1 Enable Failure 122 Incomplete Pumpdown Circuit No. 2 123 Incomplete Pumpdown Circuit No. 1 129 Compressor No. 6 Failure (App. 2.07 Only) 130 Compressor No. 5 Failure (App. 2.07 Only) 131 Compressor No. 4 Failure 132 Compressor No. 3 Failure 133 Compressor No. 2 Failure 134 Compressor No. 1 Failure 153 Frost Protect Circuit No. 2 154 Frost Protect Circuit No. 1 158 Low Pressure Circuit No. 2 159 Low Pressure Circuit No. 1 166 High Pressure Circuit No. 2 167 High Pressure Circuit No. 1 170 Fan Retry 173 Heat Failure 176 Low Airflow 179 Entering Fan Sensor Problem 182 Return Air Sensor Problem 185 Space Sensor Problem 188 OAT Sensor Problem 197 Freeze Problem Siemens Building Technologies, Inc. Page 9 of 10

Current Warning (Point 129) Table 9. Current Warning s (Point 129). 0 NoActiveWarnings 4 Heating Board Hardware Warning 8 Generic Condenser Board Hardware Warning 12 Compressor Board 2 Hardware Warning 16 Compressor Board 1 Hardware Warning 20 Dirty Final Filter Warning 24 Dirty Filter Warning 28 Airflow Switch Warning Information in this document is based on specifications believed correct at the time of publication. The right is reserved to make changes as design improvements are introduced. Product or company names mentioned herein may be the trademarks of their respective owners. 2004 Siemens Building Technologies, Inc. Siemens Building Technologies, Inc. 1000 Deerfield Parkway Country of Origin: US Buffalo Grove, IL 60089-4513 Page 10 of 10 U.S.A.