STRUCTURAL PERFORMANCE TEST REPORT

Similar documents
Citizens Opening Protection Requirements for Homes in the Wind-Borne Debris Region (WBDR)

C E R T I F I C A T E O F C O M P L I A N C E

FLORIDA BUILDING COMMISSION MEETING July 10, 11 and 12, 2006 Hard Rock Hotel Seminole Indian Country, FL

Connecting Garage Door Jambs to Building Framing

#161. Connecting Garage Door Jambs to Building Framing. Introduction

Installation Analysis

TCO K [LAB #6] Module Case Team Studies

Alan's Factory Outlet Carport Prices in Colorado, New Mexico, Nebraska & Nevada NOTE: FRAME WORK LENGTH 20, 25, 30, 35, 40, 45, 50.

Hurricane Deductible

Structural Failure(s) MET Wind Flowing Around a House. Shutters. Breaching the Building Envelope Adds Internal Pressure to External Suction

MINUTES PRODUCT APPROVAL PROGRAM OVERSITE COMMITTEE PRESENT: PRODUCT APPROVAL PROGRAM OVERSITE COMMITTEE NOT PRESENT: STAFF PRESENT: OTHERS PRESENT:

Keeping Up with the changes in Testing, Certification and Product Approval Programs

Installation Guide. Product Code: DLCEL. T: F: Page 1 of 5 PRODUCT #: DLCEL

e-tender Providing and fixing Modular Partition & Roller curtain Important Information: BID FORM for Procurement of

THE CLARIDGE OF POMPANO CONDOMINIUM, INC. ARCHITECTURAL REVIEW COMMITTEE REQUEST FOR MODIFICATION PART A - COMPLETED BY OWNER

Model H-340. Tipping Bucket Rain Gauge. Owner's Manual Version 1.1

5. OPTIONAL SECTION I - COVERAGES & ENDORSEMENTS: 5-c BUILDING ADDITIONS AND ALTERATIONS - (ML-51)

HAZUS-MH Hurricane Model Methodology. II: Damage and Loss Estimation

The Florida Public Hurricane Loss Model Selected Results

Limited Warranty (FOR PRODUCTS PURCHASED AFTER JANUARY 17, 2018)

Hurricane Charley - Executive summary. Hurricane Charley. Nature s Force vs. Structural Strength

Shear Wall Design with Examples DES 413-1

Barn Garage. OWNER S MANUAL / Instructions for Assembly Size 13 Ft x 18 Ft / 3.9 Mtr. x 5.5 Mtr. (Approx.) USP US POLYMERS INC

FIRE RESISTANCE OF A SLIDING ACCORDION DOOR ASSEMBLY. This report replaces FAR 3847 issued on the 2 April 2012

IRC Bracing Methods, Relevant Test Data, and Recommended Design Values for Wind Bracing Analysis of Conventional Wood-Frame Homes

Wind Loss Mitigation Implementation Issues and Recommendations

BID RESPONSE LABEL THIS LABEL FOR USE WITH UNITED STATES POSTAL SERVICE DELIVERY PURCHASE OF SIGNS AND SIGN ACCESSORIES (DATE): NOV.

MASSACHUSETTS PROPERTY INSURANCE UNDERWRITING ASSOCIATION (MPIUA)

Who We Are. Meet Our CEO WRIGHT S. How Can We Help? Richard J. Kurtz

Exterior Vinyl Colors (White, Tan, Clay or Woodgrain Interiors) Interior Woodgrains (White, Tan, Clay or Factory-applied Color Exteriors)

Policy Title: Historic Downtown Patio Policy

EXHIBIT A IWFA POLICIES & PROCEDURES. Endorsed Testing Standards and Methods

Announcement Announcement/Light Legend Light Usage Recommendation Green Yellow Red Ride & Drive Only! N/A N/A Ride & Drive with Caution Announcement!!

apogee enterprises, inc. Investor Presentation

RFP # for Addition to Parks Recreation 190 Facility

ST. TAMMANY PARISH PATRICIA P. BRISTER PARISH PRESIDENT

Architectural Guidelines Ref: Apopka Airport Web Page (Select Board & Committee Chairs / Architectural Review)

Pre Installation checklist SAFETY INSTRUCTIONS

MASSACHUSETTS PROPERTY INSURANCE UNDERWRITING ASSOCIATION

In this document, capitalised terms have the meaning given in the Member Agreement and Owner Supplement. What does this policy cover?...

Your guide to Buildmark

Solicitation 640. Recycling Bins. Bid Designation: Public

AIR Worldwide Analysis: Exposure Data Quality

NEW. Multifunction frame plug MFR. The all-rounder for your projects. Fire resistance class F 90 see approval

Solid-Electrolyte TANTALEX Capacitors, Hermetically-Sealed, Axial-Lead

Sensitivity Analyses: Capturing the. Introduction. Conceptualizing Uncertainty. By Kunal Joarder, PhD, and Adam Champion

SEPTA Roadway Pavement Markings Specification

OCTANORM SHELL SCHEME

G r a d e 1 1 E s s e n t i a l M a t h e m a t i c s ( 3 0 S ) Midterm Practice Exam Answer Key

Access Fasteners Vic. Ph: (03) FAX: (03) W.A. Ph: (08) FAX (08)

Ø mm. SYSTEM KAN-therm. High quality for reasonable price TECHNOLOGIA SUKCESU ISO 9001

REQUEST FOR BID POLE BUILDING CONSTRUCTION

Hydraulic Series Coupon Holders

Pella Entry Door System Limited Lifetime Warranty

County Barn Road RPUD. Deviation Justification

CHIPS CROSSING HOMEOWNERS ASSOCIATION ARCHITECTURAL CONTROL COMMITTEE GUIDELINES AND INSTRUCTIONS. Revised 07/15/09

SHELL SCHEME EXTRAS ORDER FORM & GRID PLAN FORM

FREEDOM PARK SUMMARY BACKGROUND

2019 MIBS EXHIBITOR MANUAL

PAPER TOWEL DISPENSER Installation Instructions AGPTD16

HCG PURCHASING CO-OP INVITATION TO BID

LIMITED WARRANTIES. IT PAYS TO COMPARE.

ROLLINGSHIELD a c c o r d i o n s

Taking the Wind Out of Hurricane Damage

OHIO DEPARTMENT OF TRANSPORTATION. PROPOSAL for the GEOTECHNICAL EXPLORATION <COUNTY-ROUTE-SECTION> <PID>

The City of Lake Forest Historic Preservation Commission Proceedings of the July 24, 2013 Meeting

201 Wolf Drive P.O. Box 87 Thorofare, NJ Phone: Fax:

REQUEST FOR PROPOSALS

Mechanical Design of Process Equipments

Windstorm Insurance in Florida Protect Our Economy

Level 3 Reserve Study without a Site a Site Visit Visit

Welcome to trim that differentiates.

APPRAISAL_PLUS_CRAW_ PDF. Date 2/21/2017 INSURED

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

Fish Farm Proposal Form (Marine & Freshwater Sites)

Structural Calculations

WOODSTONE PRODUCT WARRANTY

Policy E-06: Added (c) to reflect policy (no change). April 1, 2013 Policy E-09: Added more information to reflect changes in QFR process.

OVERALL DIA. RIM WIDTH OVERALL WIDTH

The Grande Phoenician at the Grande Preserve Condominium Association, Inc.

Purchasing Department

SVL. 250 For full technical and ordering information visit

MANAGEMENT PLAN. 252 East Highland Avenue Milwaukee, WI A T DREXEL TOWN SQUARE

101 LOGISTICS AVENUE, JEFFERSONVILLE, IN 47130

Fundo Integro NEW. The slimmest standard-compliant complete wedi shower system.

Volusia County Floodplain Management Plan 2012

Hurricane Preparedness

PLEASE READ ALL SPECIFICATIONS AND REQUIREMENTS OF THIS BID CAREFULLY AS CHANGES, ADDITIONS OR DELETIONS TO THIS BID MAY HAVE BEEN MADE.

C ONSISTENT TENT, ARDS

Stylos INSTALLATION INSTRUCTIONS

THERMAX Wall System Gold Warranty 15 year Thermal + 15 year Water Resistance + 6 month Exposure

Best Wishes for the New Year!

Solid-Electrolyte TANTALEX Capacitors Hermetically-Sealed, Axial-Lead FEATURES Terminations: Tin/lead (SnPb), 100 % Tin (RoHS compliant)

Conducting a Facilities Condition Assessment as Part of Your Capital Planning. FEFPA July 5, 2011

INVITATION TO BID # 465

AEROSPACE PRODUCT LINE PACKAGE BROCHURE

Presenters. Bracken Engineering. Structures Disasters Forensics

VENTUS. Let the. breeze in.tm

STATEMENT OF REASONS DECISION

DRC gross price list (end customers) EUROPE

Transcription:

STRUCTURAL PERFORMANCE TEST REPORT Client: Gallina USA, LLC. 245 E Madison Avenue Milton, WI 53563 Report No.: NCTL-210-3193-2 Test Date: 10/12/05 Report Date: 10/26/05 Test Specimen: 0.280 (7mm) Corrugated Onda Plus Storm Panel (43 x 96 - D/P Positive 40psf and Negative 40psf). Test Method: ASTM E330-02, Test Method for Structural Performance of Exterior Windows, Curtain Walls, and Doors by Uniform Static Air Pressure Difference. ASTM E1886-99, Standard Test Method for Performance of Exterior Windows, Curtain Walls, Doors and Storm Shutters Impacted by Missile and Exposed to Cyclic Pressure Differentials. ASTM E1996-02, Standard Specification for Performance of Exterior Windows, Curtain Walls, Doors, and Storm Shutters Impacted by Windborne Debris in Hurricanes. TEST SPECIMEN DESCRIPTION General: The specimen tested was a 0.280 (7mm) corrugated onda plus storm panel, which consisted of one (1) sheet of cross-fluted polycarbonate. The overall dimensions were 43 wide x 96 high x 0.280 thick. Both interior and exterior skin walls measured 0.030 in thickness. The interior fluted walls, measured 0.010 in thickness. Installation: Each F track was anchored with four (4) 1/4 x 2.5 hex head Tapcons located 6 from each end and 10.33 thereafter. Each hurricane storm panel was installed into the test buck with an extruded aluminum flat F track at the head and sill. The panel was captured with six (6) 1/4 x 20 x 1.5-18.8 square head machine screws with 1/4 x 20 wing nut and two (2) 1/4 x 1.250 x 1/8 rubber washers at the head and sill, located 2.5 down and every corrugation. Interior and Exterior Surface Finish: The interior and exterior surface finish was translucent plastic. TEST RESULTS Specimen # 1 Title of Test and Method Measured Allowed Uniform Load Structural - ASTM E330 Loc. #1 Loc. #1 75.0 psf Exterior 0.021 0.056 75.0 psf Interior 0.032 0.056 Loc. # 1 - Center between Fasteners at the Head Loc. # 1 - Maximum Allowable Permanent Set (0.004 x 7 length of span) = 0.028

Gallina USA, LLC Page 2 of 6 NCTL-210-3193-2 TEST PARAMETERS The appropriate missile to be used for impact tests was selected in accordance with section 6 of ASTM E1996 based on the following criteria: Level of Protection: Wind Zone: Assembly Height Above Ground Level: Basic Protection Wind Zone 4 - greater than 140 mph Less than or equal to 30 feet IMPACT TEST RESULTS Large missile impact tests were conducted using a #2 Southern Yellow Pine 2 x 4 measuring 92 in length and weighing 9.25 lbs (Missile D) as shown in Table 2 of ASTM E 1996. Missile speeds and locations were in accordance with section 5.3 and Table 2 ASTM E1996. For pass/fail criteria, no penetration is defined as no tear longer than 5 inches in length and 1/16" wide or no opening through which a 3 diameter solid sphere can freely pass per section 7 of ASTM E 1996. All specimens were conditioned at 70º F ± 15ºF prior to testing. Missile orientation at impact complies with section 11.2.2 of ASTM E1886. Specimen # 2 Impact No. Impact Location Missile Speed Results 1 Center of Panel 50 feet/sec 2 Top Right Corner of Panel 50 feet/sec Specimen # 3 Impact No. Impact Location Missile Speed Results 1 Bottom Left Corner of Panel 50 feet/sec 2 Center of Panel 50 feet/sec Specimen # 4 Impact No. Impact Location Missile Speed Results 1 Top Right Corner of Panel 50 feet/sec 2 Center of Panel 50 feet/sec NOTES: All impacts were rejected without penetration. Upon completion of testing the specimen met the requirements for ASTM E 1996-02. The conditioning temperature of the specimens were 72.5. Missile orientation at impact complies with Section 11.2.2 of ASTM E1886-02.

Gallina USA, LLC Page 3 of 6 NCTL-210-3193-2 PRESSURE CYCLING TEST RESULTS After completion of the impact tests, the specimens were pressure cycled in accordance with Table 1 of ASTM E1996. The duration of each air pressure cycle was between 1 and 5 seconds. Where required, two (2) mil plastic film was used to obtain cycle loads. The film did not affect the performance of the specimen or influence the results of the test. For pass/fail criteria, no opening is defined as no tear longer than 5 inches in length and 1/16" wide or no opening through which a 3 diameter solid sphere can freely pass per section 7 of ASTM E 1996. Specimen # 2 Design Pressure + 40psf -40psf Positive Loading Range Pressures No. of Cycles Results 0.2 DP to 0.5 DP 8.0 psf to 20.0 psf 3500 Passed 0.0 DP to 0.6 DP 0.0 psf to 24.0 psf 300 Passed 0.5 DP to 0.8 DP 20.0 psf to 32.0 psf 600 Passed 0.3 DP to 1.0 DP 12.0 psf to 40.0 psf 100 Passed Negative Loading Range Pressures No. of Cycles Results -0.3 DP to -1.0 DP 12.0 psf to 40.0 psf 50 Passed -0.5 DP to -0.8 DP 20.0 psf to 32.0 psf 1050 Passed -0.0 DP to -0.6 DP 0.0 psf to 24.0 psf 50 Passed -0.2 DP to -0.5 DP 8.0 psf to 20.0 psf 3350 Passed Specimen # 3 Design Pressure + 40psf -40psf Positive Loading Range Pressures No. of Cycles Results 0.2 DP to 0.5 DP 8.0 psf to 20.0 psf 3500 Passed 0.0 DP to 0.6 DP 0.0 psf to 24.0 psf 300 Passed 0.5 DP to 0.8 DP 20.0 psf to 32.0 psf 600 Passed 0.3 DP to 1.0 DP 12.0 psf to 40.0 psf 100 Passed Negative Loading Range Pressures No. of Cycles Results -0.3 DP to -1.0 DP 12.0 psf to 40.0 psf 50 Passed -0.5 DP to -0.8 DP 20.0 psf to 32.0 psf 1050 Passed -0.0 DP to -0.6 DP 0.0 psf to 24.0 psf 50 Passed -0.2 DP to -0.5 DP 8.0 psf to 20.0 psf 3350 Passed

Gallina USA, LLC Page 4 of 6 NCTL-210-3193-2 Specimen #4 PRESSURE CYCLING TEST RESULTS Con t Design Pressure + 40psf -40psf Positive Loading Range Pressures No. of Cycles Results 0.2 DP to 0.5 DP 8.0 psf to 20.0 psf 3500 Passed 0.0 DP to 0.6 DP 0.0 psf to 24.0 psf 300 Passed 0.5 DP to 0.8 DP 20.0 psf to 32.0 psf 600 Passed 0.3 DP to 1.0 DP 12.0 psf to 40.0 psf 100 Passed Negative Loading Range Pressures No. of Cycles Results -0.3 DP to -1.0 DP 12.0 psf to 40.0 psf 50 Passed -0.5 DP to -0.8 DP 20.0 psf to 32.0 psf 1050 Passed -0.0 DP to -0.6 DP 0.0 psf to 24.0 psf 50 Passed -0.2 DP to -0.5 DP 8.0 psf to 20.0 psf 3350 Passed Description of specimens after cycle: Specimens showed no resultant failure or duress. Criteria 7.1.1 With no tear formed longer than 5 or no opening formed through which a 3 diameter solid sphere can freely pass. Testing Observed by: Mr. Daniel Ocasio (NCTL) Mr. Rick Moffett (NCTL) Mr. Jim Moore (PTC.) Mr. Frank Meints (Gallina USA, LLC.) Sampling: The sampling of the product(s) in this test report was accomplished by the client in accordance with the specification(s) the sample was tested to. The listed results were secured by using the ASTM E1886 test method and indicate compliance with the performance requirements of ASTM E1996 for the listed test parameters at the following design pressures: Positive Design Pressure: Negative Design Pressure: + 40.0 psf - 40.0 psf TEST COMPLETED 10/12/05

Gallina USA, LLC Page 5 of 6 NCTL-210-3193-2 Detailed drawings were available for laboratory records and compared to the test specimens at the time of this report. A copy of this report along with representative sections of the test specimens will be retained by NCTL. The results obtained apply only to the specimens tested. No conclusions of any kind regarding the adequacy or inadequacy of the glass in the test specimens may be drawn from this test. This report does not constitute certification of the product, which may only be granted by a certification program validator. NATIONAL CERTIFIED TESTING LABORATORIES Daniel Ocasio Technician Christopher Bennett Division Manager Gerard J. Ferrara, P.E. Florida Registration No. 11985 Certificate of Authorization No. 2529 200 West Wisconsin Avenue Deland, Florida 32720 (386) 734-8792 - PHONE (386) 734-8692 - FAX DO/mjt

ASTM E1996 COMPLIANCE STATEMENT On October 12 th, 2005, Gallina USA, LLC. completed impact testing at National Certified Testing Laboratories in Orlando, FL. All tests were performed in full accordance with ASTM E1886 and ASTM E1996 with no deviations. Manufacturer: Product Series: Product Configuration Tested: Tested Size: Glazing Configuration: Gallina USA, LLC. 0.280 (7mm) Corrugated Onda Plus Storm Panel. Single Panel 48 x 96 overall N/A Level of Protection: Basic Protection Wind Zone: Wind Zone 4 - Greater than 140 mph Assembly Height above Ground: Less than or equal to 30 feet Impact Missile Used: Positive Design Pressure: Negative Design Pressure: Missile D + 40 psf - 40 psf See NCTL Report 210-3193-2 for complete specimen description and test results. NATIONAL CERTIFIED TESTING LABORATORIES Daniel Ocasio Technician Christopher Bennett Division Manager